Permit Information
Permit NumberFIR18-00756
StatusIssued
Name PROTEX
Site Address 2800 S MAPLE GROVE RD
Project NameMaple Grove Elementary TI
Customer Number 
ePlanReviewYes
Description
Upgrade existing fire system to code-compliant voice system. This project consists of constructing a 12,003 sq. ft. addition to an existing 45,000 sq. ft. elementary school. This work is associated with building permit BLD18-00776.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/22/20198/23/20198/23/2019ACANC
DetailsTroy Cobbley
I have not received confirmation that Alarmco has installed the antenna for the AES. Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan assigned to (Lee)8/15/2019 8/16/2019 DONE
DetailsLee G Meredith
as built
Alarm Plan Check8/16/2019 8/16/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/16/2019 DONE
As built - No fee.
Permit Ready to Issue  8/16/2019 DONE
CHANGE STATUS TO (ISS)  8/16/2019 DONE
INSP-Final Inspection8/15/20198/15/20198/15/2019PPART
DetailsMark Scharfen
Tested devices and signals. AES has low battery trouble. Verified sprinkler tie in, duct detector shutdown and notification in new school. OK for temp pending plan mod updating candella. Will need to test other fire alarm permit on existing school.

Contact is Dan. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten
Plan resubmittals received  8/15/2019 DONE
as built request to open by Morgan
Plan assigned to (Lee)8/12/2019 8/14/2019 DONE
DetailsLee G Meredith
Alarm Plan Check8/14/2019 8/14/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/14/2019 DONE
As built - No fee.
Permit Ready to Issue  8/14/2019 DONE
CHANGE STATUS TO (ISS)  8/14/2019 DONE
Plan Modification Accepted  8/12/2019 DONE
as built requested by Morgan from Protex
INSP-Final Inspection8/9/20198/9/20198/9/2019PFAIL
DetailsMark Scharfen
Tested panel functions. AES is at NETCON 0 per Alarmco CS. Tested trouble and alarm signal. Speaker in FACP room is horn, needs to be a speaker. Outside speaker strobe by bell needs to be a strobe only. No lift on site. AES zone wire is not shielded. Unable to verify gym devices.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection8/8/20198/8/20198/8/2019PCANC
DetailsTroy Cobbley
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
1st review completed  10/10/2018 PASS
Alarm Plan Check10/8/2018 10/10/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/10/2018 DONE
Plans approved with review comments and requirements.
Permit Ready to Issue  10/10/2018 DONE
met
Issue and Print Permit  10/10/2018 DONE
Miscellaneous action  10/8/2018 DONE
Emailed Morgan to request that he add a scale graph to his drawing. Revised drawing received 10-9-18.
Application received  10/1/2018 DONE
Application submitted via PDS Online on Oct 1 2018 3:04PM