INSP-Final Inspection | 12/18/2018 | 12/19/2018 | 12/19/2018 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 12/17/2018 | 12/20/2018 | 12/18/2018 | A | CANC |
Troy Cobbley
|
|
|
This inspection will be with our technician Eric Nelson ###-####. Phone #: ###-#### >> Inspection requested via web by Cheyenne Zumstein Inspection cancelled from web by: Cheyenne Zumstein
|
Miscellaneous action | | | 12/11/2018 | | DONE |
|
|
|
As built drawings received. They appear to be accurate and require on site review by the inspector to verify they match the actual installation. Applicant is requried to have a copy of the as built drawings on site at the time of inspection.
|
INSP-Final Inspection | 11/13/2018 | 11/14/2018 | 11/14/2018 | A | PART |
Troy Cobbley
|
|
|
A temporary for this fire alarm permit is being given until a horn/strobe is added in the Conference Room. Room was originally a office but the use has changed.
|
INSP-Final Inspection | 11/12/2018 | 11/13/2018 | 11/13/2018 | A | FAIL |
Troy Cobbley
|
|
|
No access to the fire alarm panel. Lock is brocken. Will need to be rescheduled.
|
INSP-Final Inspection | 11/7/2018 | 11/8/2018 | 11/8/2018 | P | FAIL |
Troy Cobbley
|
|
|
One strobe is overspaced at the front of the store, strobe coverage is needed in the back of the Sales floor
|
Issue and Print Permit | | | 10/17/2018 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 10/5/2018 | | 10/8/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 10/8/2018 | | PASS |
|
|
|
|
Alarm Plan Check | 10/5/2018 | | 10/8/2018 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 10/8/2018 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 10/8/2018 | | DONE |
|
|
|
met
|
Application received | | | 10/5/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Oct 5 2018 11:22AM
|