Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR18-00787
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 4427 W ALPINE ST
Project NameFELL RESIDENCE
Customer Number 
ePlanReviewYes
Description
[Fell Residence]
The fire sprinkler scope of work consists of a new single family two level home. The system is designed as a passive purge system. The system utilizes CPVC piping and residential type sprinklers.

[BLD18-02411]
Permit for the construction of a new 2689 sq. ft., two stories (first story 1168 sq. ft., second story 1521 sq. ft.) single family dwelling with 4 bedrooms, 4 bathrooms, approximately 96 sq. ft. of covered patio/porch and a 1040 sq. ft. attached garage per the approved plans and any notations. R-1C zoning and setbacks per planning. JJN

Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.

• There are no AMM at this time
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/20/20195/21/20195/21/2019PPASS
DetailsTroy Cobbley
Permit finaled.

Robert Chambers is the contact. He request that he be given a call an hour before the inspection so he can meet the inspector at the site. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection5/17/20195/21/20195/20/2019PCANC
DetailsTroy Cobbley
Colton Cox is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
Staff review5/16/20195/16/20195/17/2019 PASS
DetailsMark Stumbaugh
plan mod
Plan assigned to (Stumbaugh)5/16/2019 5/17/2019 DONE
DetailsMark Stumbaugh
plan mod
PLANS/APPL TAKEN TO FRONT DESK  5/17/2019 DONE
DetailsMark Stumbaugh
Plan Mod Fee $150.00
Permit Ready to Issue  5/17/2019 DONE
CHANGE STATUS TO (ISS)  5/17/2019 DONE
plan mod
INSP-Final Inspection5/15/20195/16/20195/16/2019PFAIL
DetailsTroy Cobbley
The wrong size of underground supply is still an issue. Need to flow water flow switch and test outside alarm bell.


Marcus Smith is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
Plan Modification Accepted  5/16/2019 DONE
per customer-plan mod started in e plan-assigned to MAS
INSP-Final Inspection5/15/20195/16/20195/15/2019ACANC
DetailsTroy Cobbley
Marcus Smith is the contact. Thank you for the hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in12/13/201812/17/201812/17/2018APASS
DetailsTroy Cobbley
Rough-in passed. Tenting passed. Piping is ok for cover. Supply piping size to the backflow preventor does not match plans and will need addressed prior to a final sign off.


Marcus Smith is the contact for this RTC inspection. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
CHANGE STATUS TO (ISS)  11/28/2018 DONE
plan mod fees paid
(F) Reprint permit  11/28/2018 DONE
Plan Modification Accepted  11/21/2018 DONE
DetailsTim Frost
Plan assigned to (Tim)11/21/2018 11/21/2018 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  11/21/2018 DONE
DetailsTim Frost
Permit Ready to Issue  11/21/2018 DONE
plan mod approved
INSP-Sprinkler Rough-in11/7/201811/13/201811/13/2018PCANC
DetailsTroy Cobbley
Per the fitter the revised plans have not been approved yet. No inspection was performed.

Phone #: ###-#### Inspection requested via web by Stan Beus
Issue and Print Permit  10/22/2018 DONE
Intake Approval  10/19/2018 PASS
DetailsTim Frost
Plan assigned to (Tim)10/19/2018 10/19/2018 DONE
DetailsTim Frost
Sprinkler Plan Check10/19/2018 10/19/2018 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  10/19/2018 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  10/19/2018 DONE
DetailsTim Frost
Permit Ready to Issue  10/19/2018 DONE
Application received  10/12/2018 DONE
Application submitted via PDS Online on Oct 12 2018 2:55PM