Permit Information
Permit NumberFIR18-00815
StatusFinaled
Name PROTEX
Site Address 3536 W HILL RD
Project NameHillside Junior High TI
Customer Number 
ePlanReviewYes
Description
Upgrade existing fire alarm system to Voice. This work is not associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/10/20195/10/20195/10/2019PPASS
DetailsTroy Cobbley
Permit finaled. Previous corrections addressed.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection5/9/20195/9/20195/9/2019PFAIL
DetailsMark Scharfen
Checked prints with cut sheets. Tested notification, gym circuit worked. On testing duct detectors, none of the fans shut down. Wires were disconnected on the fire alarm interface in the roof top unit. Protex is to fix the issue with shutdown and verify all units shut down. Next test will need to test all 5 duct detectors for shurdown.

Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten
Plan assigned to (Lee)5/7/2019 5/8/2019 DONE
DetailsLee G Meredith
1st review completed  5/8/2019 PASS
Alarm Plan Check5/8/2019 5/8/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  5/8/2019 DONE
CHANGE STATUS TO (ISS)  5/8/2019 DONE
INSP-Final Inspection5/6/20195/7/20195/7/2019AFAIL
DetailsMark Scharfen
Gym speaker circuit was not working (disabled in programming per dirk). Unable to get HVAC units running for testing shutdown. Asbuilds do not match what is installed. Gym has 115CD strobes but prints and load sheets show 110CD. Current rating doesn't match cut sheet for alarm current draw. Plans will need to be submitted as a plan mod prior to next inspection. Next inspection will have a reinspection fee.

Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten
Plan Modification Accepted  5/7/2019 DONE
Per Morgan at Protex start a plan mod workflow
INSP-Final Inspection4/29/20194/29/20194/29/2019PFAIL
DetailsMark Scharfen
No Building map at panel or remote command center. No lift to test duct detectors or check cd on strobes in gym. will reschedule.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection3/21/20193/22/20193/22/2019PPART
DetailsJim Page
Final fire alarm inspection for phase 1 TCO complete.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection3/20/20193/21/20193/21/2019PFAIL
DetailsJim Page
Pull station in riser room mounted to low. Provide city approved drawings and small documents, no city approved drawings on site. Provide document cabinet at fire panel. Provide map showing initiating devices. Only item tested is the commercial hood interface, hood suppression system reports to panel.

Partial Final for cafeteria and commons. Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Miscellaneous action  3/21/2019 DONE
Received corrected as built riser drawing
Plan Modification Accepted  3/20/2019 DONE
Per Morgan at Protex
Plan assigned to (Lee)3/20/2019 3/20/2019 DONE
DetailsLee G Meredith
1st review completed  3/20/2019 PASS
Alarm Plan Check3/20/2019 3/20/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/20/2019 DONE
As builts passed. No additional comments.
Permit Ready to Issue  3/20/2019 DONE
CHANGE STATUS TO (ISS)  3/20/2019 DONE
plan mod as built
Miscellaneous action  3/12/2019 DONE
Rob called to say the school district decided to remove interface between buildings but the seperate GSM will be kept. I told him to provide as builts when tiime for sign off.
Miscellaneous action  2/28/2019 DONE
Received product data for a GSM communicator and updated riser drawing.
Plan assigned to (Lee)10/26/2018 10/29/2018 DONE
DetailsLee G Meredith
Miscellaneous action  10/29/2018 DONE
Emailed Morgan to request ceiling heights. He responded to indicate common areas are 9 feet and gym is 28 feet.
1st review completed  10/29/2018 PASS
Alarm Plan Check10/26/2018 10/29/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/29/2018 DONE
Design passed with review comments.
Permit Ready to Issue  10/29/2018 DONE
all requirements met
Issue and Print Permit  10/29/2018 DONE
Application received  10/24/2018 DONE
Application submitted via PDS Online on Oct 24 2018 3:34PM