Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR18-00835
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 1299 N ORCHARD ST
Project NameOrchard Bank FA Improvements
Customer Number 
ePlanReviewYes
Description
Replace existing fire alarm system control panel, power supplies, initiating and notification devices. Improvement will reuse existing fire alarm wiring circuitry and match existing conductor size and color where modified or extended.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  11/20/2019 DONE
All requested documentation received and approved.
Miscellaneous action  4/15/2019 DONE
Received emails that John had with Honeywell tech support that indicated the system operates properly when notification disables are activated. Currently, the way it operates meets the UL certification of the product. Ok to final
INSP-Final Inspection4/11/20194/12/20194/12/2019AFAIL
DetailsTroy Cobbley
Permit will be ok to final when documents are provided to plan review that address the supervisory/rrouble on panel as per revios corretion


John Howard, Technician Phone #: ###-#### Inspection requested via web by John Siewert
CHANGE STATUS TO (ISS)  3/20/2019 DONE
Plan Modification Accepted  3/18/2019 DONE
1st review completed  3/18/2019 PASS
Alarm Plan Check3/18/2019 3/18/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/18/2019 DONE
Plan mod passed. No additional review comments.
Permit Ready to Issue  3/18/2019 DONE
plan mod
INSP-Final Inspection2/28/20193/1/20193/1/2019AFAIL
DetailsTroy Cobbley
See the city approved plans for a list of required corrections.


Earl Lasater, Technician Phone #: ###-#### Inspection requested via web by John Siewert
FIR-Aging Inspection2/28/20192/28/20192/28/2019PCANC
DetailsTroy Cobbley
Wrong inspection type called in.
INSP-Alarm Testing2/28/20192/28/20192/28/2019PDONE
DetailsTroy Cobbley
Earl and I did a walk through of the Basement, first floor and second floor corridor system and verified horn/strobe spacing/height.
CHANGE STATUS TO (ISS)  2/22/2019 DONE
Staff review2/21/20192/21/20192/21/2019 DONE
DetailsLee G Meredith
Plan assigned to (Lee)2/21/2019 2/21/2019 DONE
DetailsLee G Meredith
1st review completed  2/21/2019 PASS
Alarm Plan Check2/21/2019 2/21/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/21/2019 DONE
Plan mod passed. No additional comments.
Permit Ready to Issue  2/21/2019 DONE
PLAN MOD
Miscellaneous action  2/21/2019 DONE
John requested the work flow be opened to upload a plan modificaiton.
Plan Modification Accepted  2/21/2019 DONE
as per Lee M-started 2nd plan mod and assigned to Lee and staff review
INSP-Final Inspection1/15/20191/16/20191/16/2019PFAIL
DetailsTroy Cobbley
No testing of devices performed today. Inspection was only for the Basement area. Plan modifications are needed showing the correct form of communication, fire sprinkler riser device count (delete dry system), strobes are too low, wall and ceiling mount devices do not corrispond with the plans, Storage Room needs notification device modifications, batteries in the FACP do not match plans. We discussed the function of the Basement duct smoke detectors in the Mechanical Room.

Earl Lasater, Technician Phone #: ###-#### Inspection requested via web by John Siewert
Plan Modification Accepted  1/11/2019 DONE
Alarm Plan Check1/11/2019 1/11/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  1/11/2019 DONE
Plan Mod passed. No additional review comments.
Permit Ready to Issue  1/11/2019 DONE
plan mod approved
Miscellaneous action  1/10/2019 DONE
John requested work flow be reopened for a plan mod.
Issue and Print Permit  10/31/2018 DONE
Plan assigned to (Lee)10/30/2018 10/30/2018 DONE
DetailsLee G Meredith
1st review completed  10/30/2018 PASS
Passed as noted on drawings.
Alarm Plan Check10/30/2018 10/30/2018 DONE
DetailsLee G Meredith
Permit Ready to Issue  10/30/2018 DONE
Application received  10/29/2018 DONE
Application submitted via PDS Online on Oct 29 2018 3:58PM