Permit Information
Permit NumberFIR18-00931
StatusFinaled
Name MOUNTAIN ALARM
Site Address 1001 S HILTON ST
Project NameAvamere Notification upgrade
Customer Number 
ePlanReviewYes
Description
Updating existing notification devices to achieve temporal sync. This work does not appear to be associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/20/20207/27/20207/27/2020PPASS
DetailsTroy Cobbley
Permit finaled.

Phone #: ###-#### Inspection requested via web by Rose Peterson
INSP-Final Inspection6/8/20206/11/20206/10/2020PCANC
DetailsTroy Cobbley
Inspecting Technician: Ray McQueen Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
INSP-Final Inspection6/5/20206/9/20206/8/2020PCANC
DetailsTroy Cobbley
Inspecting Technician: Ray McQueen Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
Plan assigned to (Lee)2/11/2020 2/19/2020 DONE
DetailsLee G Meredith
plan mod
Plan assigned to (Lee)2/19/2020 2/19/2020 DONE
DetailsLee G Meredith
Intake Approval  2/19/2020 PASS
1st review completed  2/19/2020 DONE
Alarm Plan Check2/19/2020 2/19/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/19/2020 DONE
Plan mod passed. Minimum review fee of $65 is due.
Permit Ready to Issue  2/19/2020 DONE
DO NOT ISSUE- plan mod approved
CHANGE STATUS TO (ISS)  2/19/2020 DONE
plan mod 2 approved
Plan Modification Accepted  2/11/2020 DONE
Rose requested workflow to be re opened for plan mod
INSP-Final Inspection7/17/20197/23/20197/23/2019AFAIL
DetailsTroy Cobbley
Lee performed inspection and found that inspeciton could not be performed due to notification in the sleeping rooms not being addressed.

Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose PetersonRay McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
INSP-Final Inspection1/17/20191/22/20191/22/2019AFAIL
DetailsTroy Cobbley
Todays inspection was a walk through to verify device placement. I noted several locations where weather proof backboxes will be required, and notification added. Also in the DIning area a 75cd strobe is overspaced. No small documents are on site but per the notes available online it appears that notification may be required in all of the sleeping rooms. The fire alarm contractor is going to follow up.


Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
Plan Modification Accepted  1/17/2019 DONE
Alarm Plan Check1/17/2019 1/17/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  1/17/2019 DONE
Plan mod review passed, as noted on floor plan. No additional review comments.
Permit Ready to Issue  1/17/2019 DONE
Plan mod
CHANGE STATUS TO (ISS)  1/17/2019 DONE
Miscellaneous action  1/16/2019 DONE
Rose requested the work flow be re-opened for a plan mod.
Plan resubmittals received  12/28/2018 DONE
Alarm Plan Check12/27/2018 12/28/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/28/2018 DONE
Plan review passed with review comments and required changes.
Permit Ready to Issue  12/28/2018 DONE
met
Issue and Print Permit  12/28/2018 DONE
Plan resubmittals received  12/26/2018 DONE
Alarm Plan Check12/26/2018 12/26/2018 FAIL
DetailsLee G Meredith
Only room names have been added. The balance of corrections have not been addressed. Resubmittal required.
Plan assigned to (Lee)12/11/2018 12/12/2018 DONE
DetailsLee G Meredith
1st review completed  12/12/2018 FAIL
Returned to applicant for noted corrections. Resubmittal required.
Application received  12/11/2018 DONE
Application submitted via PDS Online on Dec 11 2018 10:34AM