DOC - Permit Finaled | | | 9/17/2019 | | DONE |
|
|
|
All testing complete.
|
INSP-Final Inspection | 9/16/2019 | 9/16/2019 | 9/16/2019 | P | PASS |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Ken Webster
Tested duct detectors and fan shutdown. All functioned properly. Verified all detectors previously too close to HVAC registers had been moved.
|
INSP-Final Inspection | 9/11/2019 | 9/12/2019 | 9/12/2019 | P | FAIL |
Jim Page
|
|
|
All audio visual devices have been inspected, all fire sprinkler related items have been inspected with no deficiencies. 6 Smoke detectors in daycare area are within 36 inches of HVAC registers, smoke detectors have to be a minimum of 36 inches away from HVAC registers.
Fire Alarm Final Phone #: ###-#### Inspection requested via web by Ken Webster
|
CHANGE STATUS TO (ISS) | | | 9/10/2019 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 9/5/2019 | | 9/6/2019 | | DONE |
Lee G Meredith
|
|
|
Plan mod / as built
|
1st review completed | | | 9/6/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 9/6/2019 | | 9/6/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 9/6/2019 | | DONE |
|
|
|
Plan mod passed.
|
Permit Ready to Issue | | | 9/6/2019 | | DONE |
|
|
|
as built approved
|
Plan resubmittals received | | | 9/5/2019 | | DONE |
|
|
|
start as built workflow per Rita at Webster Fire Protection
|
Plan assigned to (Lee) | 7/18/2019 | | 7/22/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 7/22/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 7/22/2019 | | 7/22/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/22/2019 | | DONE |
|
|
|
As built - No fee.
|
Permit Ready to Issue | | | 7/22/2019 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 7/22/2019 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/18/2019 | | DONE |
|
|
|
Requested the workflow to be opened for as built
|
Issue and Print Permit | | | 1/9/2019 | | DONE |
|
|
|
|
Alarm Plan Check | 1/8/2019 | | 1/8/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/8/2019 | | DONE |
|
|
|
Passed with review comments.
|
Permit Ready to Issue | | | 1/8/2019 | | DONE |
|
|
|
met
|
Plan assigned to (Lee) | 12/12/2018 | | 12/13/2018 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 12/13/2018 | | FAIL |
|
|
|
Failed pre-screen review. Visible notification is incorrect and ceiling heights are not shown.
|
Application received | | | 12/12/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Dec 12 2018 2:29PM
|