INSP-Final Inspection | 4/15/2019 | 4/15/2019 | 4/15/2019 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection complete.
Call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Final Inspection | 4/11/2019 | 4/12/2019 | 4/12/2019 | P | CANC |
Jim Page
|
|
|
Cancelled per conversation with point of contact, flow switch bell not hooked up, will be rescheduled for a later date.
Call James before heading out, thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Final Inspection | 4/11/2019 | 4/12/2019 | 4/11/2019 | A | CANC |
Jim Page
|
|
|
Call James when heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
Plan assigned to (Stumbaugh) | 2/4/2019 | | 2/5/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 2/5/2019 | | 2/5/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/5/2019 | | DONE |
Mark Stumbaugh
|
|
|
No Fee
|
Permit Ready to Issue | | | 2/5/2019 | | DONE |
|
|
|
plan mod approved
|
CHANGE STATUS TO (ISS) | | | 2/5/2019 | | DONE |
|
|
|
|
Plan Modification Accepted | | | 2/4/2019 | | DONE |
|
|
|
Adding a double check backflow device. Eplan workflow started.
|
INSP-Sprinkler Rough-in | 1/8/2019 | 1/10/2019 | 1/10/2019 | A | PASS |
Jim Page
|
|
|
Tenting inspection complete, all tenting in place at time of inspection, all fire sprinkler piping approved for cover.
Tenting inspection Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in/Hydro | 1/8/2019 | 1/8/2019 | 1/8/2019 | P | DONE |
Jim Page
|
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at city static pressure.
|
INSP-Sprinkler Rough-in/Hydro | 1/7/2019 | 1/8/2019 | 1/8/2019 | A | PART |
Jim Page
|
|
|
Rough in inspection for overhead fire sprinkler piping complete, areas between conditioned spaces approved for cover, tenting to be installed on attic piping at a later date, areas requiring tenting not approved for cover.
Please call Anthony before heading out, thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
Issue and Print Permit | | | 12/27/2018 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/26/2018 | | DONE |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 12/26/2018 | | 12/26/2018 | | DONE |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 12/26/2018 | | 12/26/2018 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/26/2018 | | DONE |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 12/26/2018 | | DONE |
|
|
|
met
|
Sprinkler Plan Check | 12/17/2018 | | 12/20/2018 | | FAIL |
Mark Stumbaugh
|
|
|
|
Application received | | | 12/17/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Dec 17 2018 12:45PM
|
Intake Approval | | | 12/17/2018 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 12/17/2018 | | 12/17/2018 | | DONE |
Mark Stumbaugh
|
|
|
|