Permit Information
Permit NumberFIR18-00946
StatusFinaled
Name PEAK ALARM
Site Address 1410 N ETHRIDGE LN
Project NameBoise Daycare
Customer Number 
ePlanReviewYes
Description
Provide a fire alarm system, horn strobes and system smoke detectors. The building is fully sprinklered. This work is associated with building permit BLD18-01631.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/12/20193/15/20193/15/2019APASS
DetailsJim Page
Please contact nate roughly 15 mins to arrival Phone #: ###-#### >> Inspection requested via web by jason petty

Verified all outstanding items were met.
DOC - Permit Finaled  3/15/2019 DONE
CHANGE STATUS TO (ISS)  3/12/2019 DONE
inspector didn't mean to final permit
INSP-Final Inspection3/6/20193/6/20193/6/2019AFAIL
DetailsTroy Cobbley
Tested 100% panel functionality. Sprinkler monitoring, initiaing and notification devices. Passed test. Still need updated addresses on as-built plans and building map, AC breaker lock. There was mention of access control being added before buillding is completed. Basement has a kitchen with residential hood. Class one hood may need to be added.

Nate with Peak was on site.
INSP-Final Inspection3/4/20193/5/20193/6/2019PFAIL
DetailsTroy Cobbley
Tested 100% panel functionality. Sprinkler monitoring, initiaing and notification devices. Passed test. Still need updated addresses on as-built plans and building map, AC breaker lock. There was mention of access control being added before buillding is completed. Basement has a kitchen with residential hood. Class one hood may need to be added.

Please call Nate roughly 15 minutes prior to arrival. Phone #: ###-#### Inspection requested via web by jason petty
Miscellaneous action  3/6/2019 DONE
Scope corrected in Tidemark to indicate that a voice system was not required, as indicated in the 12-27 plan mod.
Miscellaneous action  2/27/2019 DONE
Mary requested the work flow be openend to upload as builts.
Miscellaneous action  2/27/2019 DONE
per Lee M-no fees-as built
Telephone call  2/26/2019 DONE
Jeremy called to discuss return duct detector placement. He indicated that he has 3 roof top units that are all tied to a central duct. Wanted to know if 1 duct detector is adequate to use for all 3. I informed him that 1 could be used, as long as there are no duct return intakes after the single duct detector. All 3 units would shut down when the single duct detector was active. This is subbject to inspectors review of the actual installation.
INSP-Final Inspection2/18/20192/20/20192/20/2019PFAIL
DetailsTroy Cobbley
No actual testing performed. Plan mods are needed showing the actual fire alarm panel installed, a smoke detector is needed over the facp, provide verification whether hvac shutdown is needed or not, provide plan mods or make field changes to strobes that are overspaced, provide device map as per the review comments.

Nate Schneider is point of contact, please call roughly 15 minutes prior to arriving to site. ###-#### Phone #: ###-#### Inspection requested via web by jason petty
Miscellaneous action  2/7/2019 DONE
Work flow openend for upload of as builts.As builts reviewed and approved.
Issue and Print Permit  2/7/2019 DONE
plan mod approved
Permit Ready to Issue  2/7/2019 DONE
plan mod approved
CHANGE STATUS TO (ISS)  2/7/2019 DONE
Plan Modification Accepted  12/27/2018 DONE
Design originall had voice evacuation speakers with strobes. Changed to horns with strobes. Speakers not required by occupancy type and load.
1st review completed  12/27/2018 PASS
Alarm Plan Check12/27/2018 12/27/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/27/2018 DONE
Plans passed with revised comments.
Plan assigned to (Lee)12/19/2018 12/26/2018 DONE
DetailsLee G Meredith
1st review completed  12/26/2018 PASS
Alarm Plan Check12/19/2018 12/26/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/26/2018 DONE
Review passed with comments.
Permit Ready to Issue  12/26/2018 DONE
met
Miscellaneous action  12/26/2018 DONE
Mary emailed to inform that the design originaly submitted was incorrect. Requested that the work flow be reopened for correction upload.
Issue and Print Permit  12/26/2018 DONE
Application received  12/19/2018 DONE
Application submitted via PDS Online on Dec 19 2018 11:27AM