INSP-Final Inspection | 7/10/2019 | 7/11/2019 | 7/11/2019 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection complete.
Contact Ken Orahood ###-#### 30 min prior to final insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in/Hydro | 7/10/2019 | 7/11/2019 | 7/11/2019 | A | DONE |
Jim Page
|
|
|
Underground hydrostatic test complete.
Contact ken Orahood ###-#### 30 min prior to Hydro Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
Fees Due Hold | 7/10/2019 | | 7/10/2019 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 7/3/2019 | 7/8/2019 | 7/8/2019 | A | FAIL |
Jim Page
|
|
|
Underground supply lost 11psi during 2 hour hydro.
Contact Noemi Carrero ###-#### 30 min prior to UG Hydro Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in/Hydro | 7/2/2019 | 7/3/2019 | 7/3/2019 | A | FAIL |
Jim Page
|
|
|
Underground supply lost 10PSI during hydro test.
Contact Noemi Carrero - ###-#### 30 min prior to Hydro insp start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in/Hydro | 7/1/2019 | 7/2/2019 | 7/2/2019 | P | FAIL |
Jim Page
|
|
|
Underground lost 50PSI during 2 hour hydrostatic test.
Contact Noemi Carrero ###-#### 30 Min prior to UG Hydro Insp Start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Supply line flush | 7/1/2019 | 7/2/2019 | 7/2/2019 | A | DONE |
Jim Page
|
|
|
Main line flush complete.
Contact Noemi Carrero ###-#### 30min prior to UG Flush insp start please Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 6/20/2019 | 6/21/2019 | 6/21/2019 | P | PASS |
Jim Page
|
|
|
Remaining rough to cover inspection for undergorund supply complete, approved for cover, PIV will still need to be raised to be code compliant, will need to be completed before final sign off.
Contact Ken Orahood ###-#### 30 min prior to RTC Insp start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 2/25/2019 | 2/26/2019 | 2/26/2019 | P | PASS |
Jim Page
|
|
|
ROugh to cover inspection for undergorund supply piping complete. PIV needs to be raised to meet the requirements of NFPA 24 section 6.3.1, 32 to 40 inches above final grade. Adjustment will be verified at a later date.
Contact Ken Orahood ###-#### 30 min prior to UG RTC Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
Override - Parcel Holds | | | 2/8/2019 | | |
|
|
|
|
Issue and Print Permit | | | 2/8/2019 | | DONE |
|
|
|
|
Application received | | | 2/7/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Feb 7 2019 12:56PM
|
Intake Approval | | | 2/7/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 2/7/2019 | | 2/7/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 2/7/2019 | | 2/7/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/7/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Override - Parcel Holds | | | 2/7/2019 | | |
|
|
|
|
Permit Ready to Issue | | | 2/7/2019 | | DONE |
|
|
|
met
|