INSP-Final Inspection | 7/19/2019 | 7/19/2019 | 7/19/2019 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection is complete.
|
INSP-Final Inspection | 7/15/2019 | 7/16/2019 | 7/16/2019 | P | CANC |
Jim Page
|
|
|
Inspection request has been cancelled per conversation with point of contact, a follow up inspection has been coordinated f and approved for 19JULY2019 at 7AM for a full notification inspection.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 7/14/2019 | 7/15/2019 | 7/15/2019 | P | PART |
Jim Page
|
|
|
Inspected all tamper switches in fire pump room as well as pump power loss, all reported to the panel.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
Plan assigned to (Lee) | 6/24/2019 | | 7/10/2019 | | DONE |
Lee G Meredith
|
|
|
Plan mod - As Built
|
1st review completed | | | 7/10/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 7/10/2019 | | 7/10/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/10/2019 | | DONE |
|
|
|
As built passed. No fee.
|
CHANGE STATUS TO (ISS) | | | 7/10/2019 | | DONE |
|
|
|
plan mod as built- no fee per Lee
|
Permit Ready to Issue | | | 7/10/2019 | | DONE |
|
|
|
plan mod accepted
|
CHANGE STATUS TO (ISS) | | | 7/10/2019 | | DONE |
|
|
|
|
Plan Modification Accepted | | | 6/24/2019 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/11/2019 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 2/8/2019 | | 2/8/2019 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 2/8/2019 | | DONE |
|
|
|
S1 occupanciy does not require notification. Previously, the owner has elected to provide audiblility in the S1 portion of the building. This new design adds strobes to the new area and replaces the fire alarm panel. Previously spoke with Adam regarding the strobes. Told him that they would be allowed if the new area was seperated nad there were no changes to the existing system and structure. If changes took place, entire system would need to add strobes. This submittal indicates that changes were being made to the existing which would drve the full upgrade. Discussed the situation with Jason Blais. He felt that if the owner has future plans to add strobes throughout, strobe coverage in this protion would be allowed. If not, they should stay with the audible throughout to match existing. Informed Adam of this and he will address it with the owner.
|
Telephone call | | | 2/8/2019 | | DONE |
|
|
|
Adam called to say he discussed the options of audio only vs. adding strobes with the intent of eventually adding them throughout with the design team and Western Power Sports design representitive. The owners plan is to start adding visible notification throughout, in future projects.
|
1st review completed | | | 2/8/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 2/8/2019 | | 2/8/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 2/8/2019 | | DONE |
|
|
|
Plans approved with review comments and noted requirements.
|
Permit Ready to Issue | | | 2/8/2019 | | DONE |
|
|
|
met
|
Application received | | | 2/7/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Feb 7 2019 7:36PM
|