Permit Information
Permit NumberFIR19-00098
StatusFinaled
Name STATEFIRE DC SPECIALTIES
Site Address 7064 W STATE ST
Project NameNorthgate Dry Syst. Monitoring
Customer Number 
ePlanReviewYes
Description
THE SCOPE OF WORK IS TO PROVIDE MONITORING FOR VALVES ON NEW DRY SYSTEMS BEING INSTALLED BY OTHERS TO REPLACE EXISTING ANTIFREEZE SYSTEMS. TWO OF THE EXISTING ZONES PREVIOUSLY USED FOR THE EAST AND WEST ANTIFREEZE LOOP WILL BE RE-PURPOSED FOR TWO OF THE NEW DRY SYSTEM VALVES. NEW POPIT MODULES WILL BE ADDED TO MONITOR THE REMAINING NEW DRY SYSTEM VALVES/SWITCHES. SEE FLOOR PLAN AND RISER DIAGRAM FOR ADDITIONAL INFORMATION. THE SCOPE OF THIS PERMIT COVERS RISER SYSTEM #1 (ALSO REFERRED TO AS WEST) AND RISER SYSTEM #2 (ALSO REFERRED TO AS EAST) ONLY. RISER SYSTEMS 3-5 WILL BE SUBMITTED UNDER SEPARATE PERMITS. SEE PROJECT KEY PLAN FOR LOCATIONS.

This work does is associated with building permit BLD17-01767.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/10/20195/10/20195/10/2019APASS
DetailsMark Scharfen
Passed fire alarm testing. State Fire to send in as build showing trouble instead of supervisory on tampers as panel has no supervisory function.

Doug Phone #: ###-####
Permit Ready to Issue  5/10/2019 DONE
CHANGE STATUS TO (ISS)  5/10/2019 DONE
as per Lee M-as buildt from 3/22/19 passed with no fees on 5-9-19
Plan assigned to (Lee)3/22/2019 5/9/2019 DONE
DetailsLee G Meredith
as built
INSP-Final Inspection3/28/20193/29/20193/29/2019AFAIL
DetailsJim Page
West side dry system tamper is labeled west anti-freeze, west anti-freeze tamper is not reporting to panel. FDC bell is not hooked up to alarm pressure switch on east and west dry systems.

alarm not sprinklers // Barnie Phone #: ###-####
INSP-Final Inspection3/26/20193/27/20193/27/2019ANR
DetailsJim Page
Fire sprinklers were not ready for inspection, no restricted orifice provided.

Barnie Phone #: ###-####
INSP-Final Inspection3/21/20193/22/20193/22/2019PPART
DetailsJim Page
Final fire alarm inspection for related items in Workout Anytime TI complete, remaining items on this permit that deals with shell dry system to be completed at a later date.

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug
Plan assigned to (Lee)3/22/2019 3/22/2019 DONE
DetailsLee G Meredith
Plan resubmittals received  3/22/2019 DONE
as built
Alarm Plan Check3/22/2019 3/22/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/22/2019 DONE
As built passed. No additional fee.
Permit Ready to Issue  3/22/2019 DONE
CHANGE STATUS TO (ISS)  3/22/2019 DONE
plan mod no fees per lee m
Plan assigned to (Lee)3/20/2019 3/21/2019 DONE
DetailsLee G Meredith
Alarm Plan Check3/21/2019 3/21/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/21/2019 DONE
Plan mod passed with additional review comments.
Permit Ready to Issue  3/21/2019 DONE
plan mod -do not re issue
CHANGE STATUS TO (ISS)  3/21/2019 DONE
Plan Modification Accepted  3/20/2019 DONE
plan mod requested per Stephanie Cobbley
INSP-Final Inspection3/12/20193/12/20193/12/2019PNR
DetailsJim Page
Dry systems are not ready to test, deficiencies on the fire sprinkler system needs to be corrected before fire alarm final.



Call prior to going Phone #: 2089546009 >> Inspection requested via mobile web by Kenny Leslie
Plan assigned to (Lee)2/8/2019 2/11/2019 DONE
DetailsLee G Meredith
1st review completed  2/11/2019 PASS
Alarm Plan Check2/8/2019 2/11/2019 DONE
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/11/2019 DONE
Review passed with comments.
Permit Ready to Issue  2/11/2019 DONE
met
Issue and Print Permit  2/11/2019 DONE
Application received  2/8/2019 DONE
Application submitted via PDS Online on Feb 8 2019 4:59PM