INSP-Final Inspection | 5/10/2019 | 5/10/2019 | 5/10/2019 | A | PASS |
Mark Scharfen
|
|
|
Passed fire alarm testing. State Fire to send in as build showing trouble instead of supervisory on tampers as panel has no supervisory function.
Doug Phone #: ###-####
|
Permit Ready to Issue | | | 5/10/2019 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 5/10/2019 | | DONE |
|
|
|
as per Lee M-as buildt from 3/22/19 passed with no fees on 5-9-19
|
Plan assigned to (Lee) | 3/22/2019 | | 5/9/2019 | | DONE |
Lee G Meredith
|
|
|
as built
|
INSP-Final Inspection | 3/28/2019 | 3/29/2019 | 3/29/2019 | A | FAIL |
Jim Page
|
|
|
West side dry system tamper is labeled west anti-freeze, west anti-freeze tamper is not reporting to panel. FDC bell is not hooked up to alarm pressure switch on east and west dry systems.
alarm not sprinklers // Barnie Phone #: ###-####
|
INSP-Final Inspection | 3/26/2019 | 3/27/2019 | 3/27/2019 | A | NR |
Jim Page
|
|
|
Fire sprinklers were not ready for inspection, no restricted orifice provided.
Barnie Phone #: ###-####
|
INSP-Final Inspection | 3/21/2019 | 3/22/2019 | 3/22/2019 | P | PART |
Jim Page
|
|
|
Final fire alarm inspection for related items in Workout Anytime TI complete, remaining items on this permit that deals with shell dry system to be completed at a later date.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug
|
Plan assigned to (Lee) | 3/22/2019 | | 3/22/2019 | | DONE |
Lee G Meredith
|
|
|
|
Plan resubmittals received | | | 3/22/2019 | | DONE |
|
|
|
as built
|
Alarm Plan Check | 3/22/2019 | | 3/22/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/22/2019 | | DONE |
|
|
|
As built passed. No additional fee.
|
Permit Ready to Issue | | | 3/22/2019 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 3/22/2019 | | DONE |
|
|
|
plan mod no fees per lee m
|
Plan assigned to (Lee) | 3/20/2019 | | 3/21/2019 | | DONE |
Lee G Meredith
|
|
|
|
Alarm Plan Check | 3/21/2019 | | 3/21/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/21/2019 | | DONE |
|
|
|
Plan mod passed with additional review comments.
|
Permit Ready to Issue | | | 3/21/2019 | | DONE |
|
|
|
plan mod -do not re issue
|
CHANGE STATUS TO (ISS) | | | 3/21/2019 | | DONE |
|
|
|
|
Plan Modification Accepted | | | 3/20/2019 | | DONE |
|
|
|
plan mod requested per Stephanie Cobbley
|
INSP-Final Inspection | 3/12/2019 | 3/12/2019 | 3/12/2019 | P | NR |
Jim Page
|
|
|
Dry systems are not ready to test, deficiencies on the fire sprinkler system needs to be corrected before fire alarm final.
Call prior to going Phone #: 2089546009 >> Inspection requested via mobile web by Kenny Leslie
|
Plan assigned to (Lee) | 2/8/2019 | | 2/11/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 2/11/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 2/8/2019 | | 2/11/2019 | | DONE |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 2/11/2019 | | DONE |
|
|
|
Review passed with comments.
|
Permit Ready to Issue | | | 2/11/2019 | | DONE |
|
|
|
met
|
Issue and Print Permit | | | 2/11/2019 | | DONE |
|
|
|
|
Application received | | | 2/8/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Feb 8 2019 4:59PM
|