Permit Information
Permit NumberFIR19-00116
StatusFinaled
Name WEBSTER FIRE PROTECTION
Site Address 7805 W GRATZ DR
Project NameLyle Pearson Volvo
Customer Number 
ePlanReviewYes
Description
Addition of monitor module for existing RTU-8 located in living room area. This work is associated with building permit BLD17-04568..
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/27/20193/28/20193/28/2019APASS
DetailsTroy Cobbley
Permit finaled

Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Final Inspection3/18/20193/19/20193/19/2019ANR
DetailsTroy Cobbley
I arrived and found that the existing fire alarm panel has been replaced apparently without permits by another contractor. So no testing was performed. Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Final Inspection2/25/20192/25/20192/25/2019PFAIL
DetailsJim Page
Could not verify unit shutdown after initial smoke detector test, HVAC unit appears to be de-energized. Fire alarm panel has numorous issues, panel is showing a trouble with random characters showing up on screen, panel will not annunciate with troubles or supervisory signals. Monitoring was not verified during inspection.

Tom Phone #: ###-####
Issue and Print Permit  2/25/2019 DONE
PLANS TAKEN FRONT DESK ALARM  2/22/2019 DONE
Quick permit passed. No comments. Release delayed because applicant did not provide the associated building permit number on their application. Numerous current building permits at this site so hard to tell which permit is was associated with. Applicant finally provided correct number.
Permit Ready to Issue  2/22/2019 DONE
Plan assigned to (Lee)2/19/2019 2/19/2019 DONE
DetailsLee G Meredith
1st review completed  2/19/2019 PASS
Alarm Plan Check2/19/2019 2/19/2019 PASS
DetailsLee G Meredith
Application received  2/17/2019 DONE
Application submitted via PDS Online on Feb 17 2019 8:17AM