INSP-Final Inspection | 9/13/2019 | 9/13/2019 | 9/13/2019 | P | PASS |
Mark Scharfen
|
|
|
passed fire alarm
Call ahead to kristin @ ###-####. Please have inspection 1:30 and on if possible. If its going to be earlier I need to know at least 1 hour in advance so I can find another tech to be onsite. Thank you very very much. Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
Plan assigned to (Lee) | 9/11/2019 | | 9/13/2019 | | DONE |
Lee G Meredith
|
|
|
as built
|
1st review completed | | | 9/13/2019 | | DONE |
|
|
|
|
Alarm Plan Check | 9/13/2019 | | 9/13/2019 | | DONE |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 9/13/2019 | | DONE |
|
|
|
As built - No fee.
|
Permit Ready to Issue | | | 9/13/2019 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 9/13/2019 | | DONE |
|
|
|
as built approved- no fee per Lee
|
INSP-Final Inspection | 9/10/2019 | 9/11/2019 | 9/11/2019 | A | FAIL |
Mark Scharfen
|
|
|
Plans do not match what is installed. Plans show two phone lines for monitoring. There is a DSC Cell DACT installed that is not on plans. According to JCI this was installed by Apex. Did not check horn strobe placment/candella. THere is an in duct detector in the reception area that is above hard lid ceiling with no access hatch. Per Brian, he accessed by moving the 120V lighting. I noted there were at least 4 card readers (not live) by entry doors and there is no access control interface shown on fire alarm plans. While access control integration with fire alarm wouldn't hold up fire alarm final it may hold up building life safety. I gave this information verbally to both Damien over the phone and Brian, both with JCI. General Contractor was not on site.
Call ahead to Brian ###-#### Phone #: ###-#### >> Inspection requested via web by Kristin Dolan
|
Plan resubmittals received | | | 9/11/2019 | | DONE |
|
|
|
adding dialer to plans - start as built workflow per Kristin at Johnson Controls
|
Plan assigned to (Lee) | 9/9/2019 | | 9/10/2019 | | DONE |
Lee G Meredith
|
|
|
as built
|
1st review completed | | | 9/10/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 9/10/2019 | | 9/10/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 9/10/2019 | | DONE |
|
|
|
As built - No fee.
|
1st review completed | | | 9/10/2019 | | DONE |
|
|
|
|
Alarm Plan Check | 9/10/2019 | | 9/10/2019 | | DONE |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 9/10/2019 | | DONE |
|
|
|
As built - No fee.
|
Permit Ready to Issue | | | 9/10/2019 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 9/10/2019 | | DONE |
|
|
|
as built. no fees per lee
|
Plan resubmittals received | | | 9/9/2019 | | DONE |
|
|
|
request to open as buildt by Kristen
|
Issue and Print Permit | | | 4/11/2019 | | DONE |
|
|
|
|
Alarm Plan Check | 4/2/2019 | | 4/2/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/2/2019 | | DONE |
|
|
|
Passed with comments and drawing note.
|
Permit Ready to Issue | | | 4/2/2019 | | DONE |
|
|
|
met
|
Application received | | | 3/4/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 4 2019 11:45AM
|
Plan assigned to (Lee) | 3/4/2019 | | 3/4/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 3/4/2019 | | PASS |
|
|
|
|