INSP-Final Inspection | 2/11/2020 | 2/12/2020 | 2/12/2020 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The associated permit FIR20-00069 has been finaled.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Final Inspection | 2/6/2020 | 2/7/2020 | 2/6/2020 | A | CANC |
Troy Cobbley
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, February 06, 2020.
|
INSP-Final Inspection | 2/5/2020 | 2/6/2020 | 2/6/2020 | A | FAIL |
Greg Ruxton
|
|
|
Permit failed based on noted deficiencies: induct smoke detector descriptors not correct (2nd fl ); basement riser room devices descriptors need to identify devices as being in the basement riser room. Contractor to coordinate with monitoring company to ensure accuracy of descriptors before next inspection. 2088990672 >> Inspection requested via mobile web by Josiah Froese
|
INSP-Final Inspection | 1/31/2020 | 2/3/2020 | 2/3/2020 | A | FAIL |
Troy Cobbley
|
|
|
Permit can be finaled when the permit for the fire alarm panel replacement has been inspected/finaled. Today we verified the two smoke detectors in the Basement Mech Room.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Final Inspection | 1/29/2020 | 1/29/2020 | 1/29/2020 | P | CANC |
Troy Cobbley
|
|
|
Cancel per discussion with Josiah due to issues with the fire alarm panel.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
1st review completed | | | 1/27/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 1/27/2020 | | 1/27/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/27/2020 | | DONE |
|
|
|
As built - No Fee.
|
Permit Ready to Issue | | | 1/27/2020 | | DONE |
|
|
|
as built met
|
CHANGE STATUS TO (ISS) | | | 1/27/2020 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/24/2020 | | DONE |
|
|
|
Per Dante email, Apex Boise, submitting for as builts
|
Plan assigned to (Lee) | 1/24/2020 | | 1/24/2020 | | DONE |
Lee G Meredith
|
|
|
as builts
|
INSP-Alarm Testing | 1/16/2020 | 1/17/2020 | 1/17/2020 | A | DONE |
Troy Cobbley
|
|
|
For a final sign off as-builts are needed to be approved and the building shall report out to the monitoring company with the building address for these signals.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Alarm Testing | 1/15/2020 | 1/16/2020 | 1/17/2020 | A | DONE |
Troy Cobbley
|
|
|
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
Tested duct detection and fire smoke dampers, elevator recall and shunt, basement thru floor 3 wet sprinklers in stair L, sprinkler bell, manual alarm. All operated properly. Strobes need to be installed in the trash rooms. Centeral station monitoring was not verified and some sprinkler work still needs to be verified. LGM
|
Issue and Print Permit | | | 4/2/2019 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 3/29/2019 | | 4/1/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 4/1/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 4/1/2019 | | 4/1/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/1/2019 | | DONE |
|
|
|
Plans passed with comments and requirements.
|
Permit Ready to Issue | | | 4/1/2019 | | DONE |
|
|
|
|
Application received | | | 3/29/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 29 2019 3:48PM
|