Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR19-00237
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 325 W IDAHO ST
Project NameSt. Lukes DCIP FMRI
Customer Number 
ePlanReviewYes
Description
10,500 Sq Ft 2 level bldg to be fully sprklered per NFPA 13 Code, Occupancy class B,Construction type VB
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  9/12/2019 DONE
Per passing final INSP-Final Inspection on 9/11/19 by MS
INSP-Final Inspection9/10/20199/11/20199/11/2019APASS
DetailsMark Scharfen
Tested tampers and flow switch interface with fire alarm system. Checked escutcheons. Outside bell functions. Passed. Thank-you!

Please Txt Tyler Loomis ###-#### 30 min prior to Final Insp start if you can not txt him please call Ken Orahood ###-#### and he will contact Tyler.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank
INSP-Final Inspection9/5/20199/6/20199/6/2019APART
DetailsJim Page
Partial final inspection for overhead fire sprinklers complete, fire panel is new so tampers and flow switch need to be coordinated with the fire alarm vendor to inspect/verify monitoring.

Contact Tyler Loomis ###-#### pleae Text or email tylerloomis50@gmail.com 30 min prior to Final Insp please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Final Inspection8/23/20198/27/20198/27/2019ACANC
DetailsJim Page
Contact Tyler Loomis ###-#### 30 min prior to Final Insp start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
INSP-Final Inspection8/22/20198/23/20198/23/2019ACANC
DetailsJim Page
Contact Tyler Loomis ###-#### 30 Min prior to Final Insp start please

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
INSP-Sprinkler Rough-in8/7/20198/8/20198/8/2019APASS
DetailsJim Page
Previously noted items have been repaired for rough to cover in basement area, basement area approved for cover.

Contact Tyler Loomis ###-#### 30 min prior to RTC Insp Start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in/Hydro8/6/20198/6/20198/6/2019PFAIL
DetailsJim Page
Fire sprinkler upright in mech room is 8 foot off of the wall, correct overspace issue. Install correct type hanger where grid wire is holding up the pipe. Correct areas where sammy type hangers are not installed correctly, refer to manufactures documents for listed install for sammy type hanger attatchment. Relocate sidewall head that is blocked when door is open.

Contact Tyler Loomis ###-#### 30 min prior to RTC/Hydro Insp start please..Tyler has a Dr Appt. and would like to do this around 1:30 pm if at all possible please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in/Hydro8/6/20198/6/20198/6/2019PCANC
DetailsJim Page
Contact Tyler Loomis 208-859--6589 30 min prior to RTC/Hydro Insp start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
INSP-Sprinkler Rough-in8/1/20198/5/20198/5/2019AFAIL
DetailsJim Page
Called point of contact 3 times over a 30 minute time span, all calls went straight to voicemail, mailbox was not set up so message could not be left, inspection will need to be rescheduled.

Contact Tyler Loomis - ###-#### 30 Min Prior to RTC nsp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
Plan Modification Accepted  7/11/2019 DONE
Terry requested the workflow to be uploaded up for a plan mod
Plan assigned to (Stumbaugh)7/11/2019 7/11/2019 DONE
DetailsMark Stumbaugh
Sprinkler Plan Check7/11/2019 7/11/2019 FAIL
DetailsMark Stumbaugh
Plan resubmittals received  7/11/2019 PASS
DetailsMark Stumbaugh
Sprinkler Plan Check7/11/2019 7/11/2019 PASS
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  7/11/2019 DONE
DetailsMark Stumbaugh
Plan Mod Fee $150.00
Permit Ready to Issue  7/11/2019 DONE
plan mod pleae do not re issue
CHANGE STATUS TO (ISS)  7/11/2019 DONE
plan mod
INSP-Sprinkler Rough-in7/1/20197/1/20197/1/2019PPART
DetailsTroy Cobbley
See the city approved plans for rooms marked "ok" where piping can be covered. Not all areas were available for inspection due to flooring installation. Also some rooms did not have the wips installed and have been circled with a question mark. I also noted two heads too close to one another and two heads 16' apart. They have been marked on the plans.

Contact Tyler Loomis - ###-#### 30 min prior to insp start please, he would like to schedule for around noon-ish if possible.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in5/21/20195/22/20195/22/2019APART
DetailsJim Page
Rough in inspection for overhead fire sprinkler piping complete, a follow up inspection will be required after flex heads are installed the grid before all cover can be approved. Hardlids in throughout level 1 approved for cover.

Contact Tyler Loomis ###-#### 30 Min prior to RTC Insp start please, he''s requesting an mid morning /10AM inspection time if possible.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in/Hydro5/21/20195/22/20195/22/2019ADONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Contact Tyler Loomis ###-#### 30min prior to RTC /Hydro Insp start please. He''s requesting a 10 AM insp time if at all possible.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
Plan resubmittals received  4/17/2019 PASS
DetailsMark Stumbaugh
Plan assigned to (Stumbaugh)4/17/2019 4/17/2019 DONE
DetailsMark Stumbaugh
Sprinkler Plan Check4/17/2019 4/17/2019 PASS
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  4/17/2019 DONE
DetailsMark Stumbaugh
Permit Ready to Issue  4/17/2019 DONE
met
Issue and Print Permit  4/17/2019 DONE
Sprinkler Plan Check4/9/2019 4/10/2019 FAIL
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  4/10/2019 DONE
DetailsMark Stumbaugh
Sprinkler Plan Check4/3/2019 4/9/2019 FAIL
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  4/9/2019 DONE
DetailsMark Stumbaugh
Plan resubmittals received  4/9/2019 PASS
DetailsMark Stumbaugh
Plan assigned to (Stumbaugh)4/9/2019 4/9/2019 DONE
DetailsMark Stumbaugh
Application received  4/3/2019 DONE
Application submitted via PDS Online on Apr 3 2019 3:15PM
Intake Approval  4/3/2019 PASS
DetailsMark Stumbaugh
Plan assigned to (Stumbaugh)4/3/2019 4/3/2019 DONE
DetailsMark Stumbaugh