INSP-Final Inspection | 8/7/2019 | 8/8/2019 | 8/8/2019 | P | PASS |
Jim Page
|
|
|
Previously noted except for the sync issue have been corrected, sync repair is being addressed under a seperate permit, FIR19-00588. Final inspection for this scope of work complete.
DEMIAN Phone #: ###-####
|
INSP-Final Inspection | 7/29/2019 | 8/2/2019 | 8/2/2019 | P | CANC |
Jim Page
|
|
|
Cnacelled per conversation with point of contact, not ready for final inspection, will be rescheduled for a later date.
Please make last of day inspection, we can''t set off anything until 4:00 on. Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
INSP-Final Inspection | 6/24/2019 | 6/25/2019 | 6/25/2019 | A | FAIL |
Jim Page
|
|
|
Notated city approved drawings where sound level requirements were not met per NFPA72. Need to add an A/V device in notated area on city approved drawings. Audio visual devices throughout went out of sync during inspection.
Please call 30 minutes prior. Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
INSP-Final Inspection | 5/20/2019 | 5/23/2019 | 5/23/2019 | A | CANC |
Jim Page
|
|
|
Inspection request cancelled per conversation with point of contact, fire panel had troubles that were associated with the fire alarm system that could not be repaired before inspection, this request is cancelled.
Please call 30 minutes prior to inspection - Joe ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
INSP-Final Inspection | 5/17/2019 | 5/20/2019 | 5/20/2019 | A | CANC |
Jim Page
|
|
|
Cancelled per conversation with point of contact, inspection request was suppose to be for a different day, this request is cancelled at POC request.
Please call Joe prior to coming ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
Issue and Print Permit | | | 4/11/2019 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 4/8/2019 | | 4/8/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 4/8/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 4/8/2019 | | 4/8/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/8/2019 | | DONE |
|
|
|
Passed with review comemtns.
|
Permit Ready to Issue | | | 4/8/2019 | | DONE |
|
|
|
met
|
Application received | | | 4/5/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 5 2019 2:24PM
|