INSP-Final Inspection | 7/8/2019 | 7/8/2019 | 7/9/2019 | P | PASS |
Jim Page
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
All items corrected and functional.
|
DOC - Permit Finaled | | | 7/8/2019 | | DONE |
|
|
|
|
INSP-Final Inspection | 6/27/2019 | 6/28/2019 | 6/28/2019 | A | PART |
Jim Page
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
6-28-19 All smoke detectors and pull stations tested. Most heat detectors tested. All functioned properly. 1 sounder base failed in a room that is accessible from the outside only. 3 existing notification devices that do not work and no longer required need to be removed. 1 abandonded notification power supply has had the equipment removed but abandonded wiring still exists. Abandonded wire is to be removed per NEC requirements. Reinspection required once corrections have been made.
|
INSP-Final Inspection | 6/26/2019 | 6/27/2019 | 6/27/2019 | P | CANC |
Jim Page
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, June 27, 2019.
|
INSP-Final Inspection | 6/26/2019 | 6/27/2019 | 6/26/2019 | A | CANC |
Jim Page
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Wednesday, June 26, 2019.
|
INSP-Final Inspection | 6/18/2019 | 6/20/2019 | 6/20/2019 | P | CANC |
Jim Page
|
|
|
Phone #: 208990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, June 20, 2019.
|
Alarm Plan Check | 4/11/2019 | | 4/12/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/12/2019 | | PASS |
|
|
|
Passed with comments.
|
Permit Ready to Issue | | | 4/12/2019 | | DONE |
|
|
|
met
|
Issue and Print Permit | | | 4/12/2019 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 4/10/2019 | | 4/10/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 4/10/2019 | | DONE |
|
|
|
Failed prescreen review. Missing room for city stamp and missing riser drawing. Emailed Dante to inform him of requirements and provide link to online Submittal Requirements.
|
Application received | | | 4/9/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 9 2019 2:48PM
|