Permit NumberFIR19-00255
StatusFinaled
Name PROTEX
Site Address 255 N 29TH ST
Project NameWhittier Community Center
Customer Number 
ePlanReviewYes
Description
Add Voice and initiation to new bldg located at Whittier school site. This work is associated with BLD18-03814.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/23/20199/23/20199/23/2019PPASS
DetailsJim Page
Previously noted items have been corrected, final fire alarm inspection for area of work complete.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection9/19/20199/20/20199/20/2019PCANC
DetailsJim Page
Cancelled per conversation with point of contact, technician noticed two ceiling mounted devices were wall mounted, devices used are not listed for wall mount. Inspection request will be rescheduled when corrections are made.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection9/19/20199/19/20199/19/2019PCANC
DetailsJim Page
Contact is Dan. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
Plan assigned to (Lee)9/4/2019 9/18/2019 DONE
DetailsLee G Meredith
as built
1st review completed  9/18/2019 PASS
Alarm Plan Check9/18/2019 9/18/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/18/2019 DONE
As built - No fee.
Permit Ready to Issue  9/18/2019 DONE
as built approved
CHANGE STATUS TO (ISS)  9/18/2019 DONE
INSP-Final Inspection9/4/20199/4/20199/4/2019AFAIL
DetailsJim Page
Basement fire sprinkler system is not noted on the city approved drawings. Install does not match city approved draiwngs, discussed areas that is lacking coverage in the vestibules leading to the restrooms.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan resubmittals received  9/4/2019 DONE
start as built work flow per Morgan at Protex
INSP-Final Inspection9/3/20199/3/20199/3/2019PCANC
DetailsJim Page
Inspection request cancelled per conversation with point of contact due to ground fault issue, inspection will be rescheduled after repair i made.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
1st review completed  4/19/2019 PASS
Alarm Plan Check4/19/2019 4/19/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  4/19/2019 DONE
Passed with comments and drawing notes.
Permit Ready to Issue  4/19/2019 DONE
met
Issue and Print Permit  4/19/2019 DONE
Plan assigned to (Lee)4/17/2019 4/18/2019 DONE
DetailsLee G Meredith
Application received  4/10/2019 DONE
Application submitted via PDS Online on Apr 10 2019 1:05PM