Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR19-00261
StatusFinaled
Name LARSON FIRE PROTECTION LLC
Site Address 411 W SAND DUNE LN
Project NameJAYO CONSTRUCTION- NEW RESIDEN
Customer Number 
ePlanReviewYes
Description
NFPA- 13D- WET FIRE SPRINKLER SYSTEM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/14/20205/14/20205/14/2020PPASS
DetailsJim Page
Final fire sprinkler inspection is complete.

Screened- Ron Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro5/14/20205/14/20205/14/2020ADONE
DetailsJim Page
Hydrostatic test has been witnessed at city pressure, no pressure loss observed at riser provided gauge.
INSP-Sprinkler Rough-in/Hydro5/14/20205/14/20205/14/2020APASS
DetailsJim Page
Freeze protection has been corrected by adding a pass through vent, all piping has been approved for cover.
INSP-Sprinkler Rough-in/Hydro4/30/20204/30/20204/30/2020PDONE
DetailsJim Page
Main line flush is complete, plans need to be submitted to reflect the addition of a dedicated fire line, water delivery is no longer a domestic shared system.

under ground flush // Ron Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro8/21/20198/22/20198/22/2019APART
DetailsJim Page
Most of the previously noteditems have been corrected, all arras except for the main entry approved for cover, main entry has CPVC encapsulated with foam spray in insulation, gap needs to be clear between pipe and sheetrock for freeze protection. Insulators need to provide documentation showing that the spray in foam is compatible with contacting CPVC pipe. Main entry is not approved for cover.

Ron Phone #: ###-####
INSP-Sprinkler Rough-in8/7/20198/8/20198/8/2019AFAIL
DetailsJim Page
Tenting needs to be corrected in numerous areas.

Ron-insulation Phone #: ###-####
INSP-Sprinkler Rough-in7/30/20197/31/20197/31/2019APART
DetailsJim Page
Rough in inspection for overhead fire sprinkler piping complete, sprinkler piping located between conditioned spaces approved for cover, piping in attic spaces that requires tenting is not approved for cover until tenting is installed, inspected and accepted.

Ron Larson - Rough-in for residential system Phone #: ###-####
Issue and Print Permit  5/3/2019 DONE
Permit Ready to Issue  4/30/2019 DONE
met
Sprinkler Plan Check4/30/2019 4/30/2019 PASS
DetailsMark Stumbaugh
Plan resubmittals received  4/24/2019 PASS
DetailsMark Stumbaugh
Plan assigned to (Stumbaugh)4/24/2019 4/24/2019 DONE
DetailsMark Stumbaugh
Sprinkler Plan Check4/24/2019 4/24/2019 FAIL
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  4/24/2019 DONE
DetailsMark Stumbaugh
Intake Approval  4/22/2019 FAIL
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  4/22/2019 DONE
DetailsMark Stumbaugh
Application received  4/12/2019 DONE
Application submitted via PDS Online on Apr 12 2019 11:30AM