INSP-Final Inspection | 12/12/2019 | 12/13/2019 | 12/13/2019 | A | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection complete.
Rob Chambers is the contact. Thanks for all yo do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 12/11/2019 | 12/12/2019 | 12/12/2019 | A | DONE |
Jim Page
|
|
|
Hydrostatic test for dry system complete, no pressure loss observed.
Rob Chambers is the contact. Need a 24 HR Air Test on the dry system. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 12/11/2019 | 12/12/2019 | 12/12/2019 | A | DONE |
Jim Page
|
|
|
24 hour air test witnessed for dry system, no pressure loss observed.
Rob Chambers is the contact. this is a hydro on the dry system. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 12/9/2019 | 12/11/2019 | 12/11/2019 | P | PART |
Jim Page
|
|
|
Hydrostatic test for level 1 witnessed, no pressure loss observed. 24 hour air test on dry system started at 1PM @ 41psi.
Rob is the contact. There will be 2 hydro''s to be done 1 wet and 1 dry. There is also a 24 hr air test that needs to be done for the dry system. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 10/14/2019 | 10/14/2019 | 10/14/2019 | P | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping located above suspended ceiling, southwest level 1 complete, southwest level 1 approved for cover.
Robert Chambers is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
CHANGE STATUS TO (ISS) | | | 10/14/2019 | | DONE |
|
|
|
change to ISS
|
Plan resubmittals received | | | 8/16/2019 | | DONE |
|
|
|
as built requested by Roger Adams
|
Plan assigned to (Stumbaugh) | 8/16/2019 | | 8/16/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Plan Modification Accepted | | | 8/16/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/16/2019 | | PASS |
Mark Stumbaugh
|
|
|
Plan Mod Fee $150.00
|
Permit Ready to Issue | | | 8/16/2019 | | DONE |
|
|
|
plan mod
|
INSP-Sprinkler Rough-in/Hydro | 8/7/2019 | 8/8/2019 | 8/8/2019 | P | PART |
Jim Page
|
|
|
Hydrostatic test for level 2 overhead fire sprinkler piping witnessed, no pressure loss observed.
Robert Chambers is the contact. This Hydro is for the 1st and 2nd floors. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 8/5/2019 | 8/5/2019 | 8/5/2019 | P | PART |
Jim Page
|
|
|
Hydrostatic test for FDC piping witnessed, no pressure loss observed.
Robert Chambers is the contact. He would like to do an FDC Hydro at the same time. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 8/5/2019 | 8/5/2019 | 8/5/2019 | P | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping in corridor soffits, level 2B complete, corridor soffits on level 2B approved for cover.
|
INSP-Sprinkler Rough-in | 7/30/2019 | 7/31/2019 | 7/31/2019 | A | PART |
Jim Page
|
|
|
Remaining sprinkler piping above hardlids in level 2A corridor inspected, remaining level 2A corridor piping approved for cover. Corridor soffits in north hallway siffts inspected and approved for cover, east corridor soffits were not complete, east side hallway soffits not approved for cover until finished and inspected.
Robert Chambers is the contact. This rough-in is for the 2nd floor common areas. He would like this inspection first thing in the morning, if possible. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 7/29/2019 | 7/30/2019 | 7/30/2019 | A | FAIL |
Jim Page
|
|
|
Soffits on level 2B were not completed, inspection was stopped due to this being the area of cover requested.
.
Robert Chambers is the contact. This rough-in is for the soffits on the 1st and 2nd floors. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 7/26/2019 | 7/26/2019 | 7/26/2019 | A | PART |
Jim Page
|
|
|
Tenting over sprinkler piping in the dumpster area has been corrected, dumpster area approved for cover.
|
INSP-Sprinkler Rough-in | 7/16/2019 | 7/17/2019 | 7/17/2019 | P | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping on level 1B corridor and corridor soffits complete, level 1B corridor approved for cover. Tenting in place at time of inspection for level 2B southeast stairs, southeast stair hard-lid approved for cover. Dumpster room will need the tenting adjusted to cover T to dry sidewall heads, this area cannot be covered until tenting has been corrected and inspected for compliance.
Robert Chambers is the contact. He would like this inspection for the 1st floor area B. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 7/16/2019 | 7/17/2019 | 7/16/2019 | P | CANC |
Jim Page
|
|
|
Robert Chambers is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in | 7/10/2019 | 7/12/2019 | 7/12/2019 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting on wet system, level 2B complete to include remaining interior piping for dry system complete, areas inspected are approved for cover. Southeast stairwell will need to be inspected at a later date, no tenting installed in this area at time of inspection, cover is not approved for southeast stairwell.
Robert Chambers is the contact. This rough-in is for the 2nd floor area B Tinting. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 7/9/2019 | 7/10/2019 | 7/10/2019 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping above drop ceiling on level 1B complete resident rooms complete, levl 1B resident rooms approved for cover. ROugh to cover ispection for hallway soffits on level 2A complete, hallway soffits on level 2A approved for cover.
Robert Chambers is the contact. This rough-in inspection is for the 1st and 2nd floor soffits. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 7/1/2019 | 7/2/2019 | 7/2/2019 | P | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting above northwest stairs complete, area inspected approved for cover.
Robert Chambers is the contact. This rough-in inspection is for the 2nd floor area A. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 6/26/2019 | 6/27/2019 | 6/27/2019 | P | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping above lowered hardlids in kitchen/dining/living room complete, area inspected approved for cover. Exterior battered wall on southwest corner of Area A is filled with non-combustible insulation, area inspected approved for cover. As-builts need to show deleted heads that will no longer be in the area filled with insulation.
Robert Chambers is the contact for this inspection. This rough-in is for the 1st floor area A section 2. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 6/19/2019 | 6/20/2019 | 6/20/2019 | A | PART |
Jim Page
|
|
|
Rough to ocver inspection for level 2 A overhead fire sprinkler piping/tenting complete, dry system inspection for 2A has been inspected as well, section 2A approved for cover.
Robert Chambers is the contact. He asked for a 9AM inspection if possible and to please call him. This Final is for the 2nd Floor-Area A- RTC Tinting Inspection. Thank you for your help! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 6/14/2019 | 6/18/2019 | 6/18/2019 | A | PART |
Jim Page
|
|
|
Rough to cover ispection for remaining piping above hardlids on level 1 complete, hardlids on level 1 approved for cover.
Robert Chambers is the contact for this RTC/ Hydro inspection on the 1st Floor. He is hoping for an appointment around 9AM. We appreciate your help. Have a nice day Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 6/14/2019 | 6/17/2019 | 6/14/2019 | A | CANC |
Jim Page
|
|
|
Robert Chambers is the contact for this RTC/ Hydro inspection on the 1st Floor. He is hoping for an appointment around 9AM. We appreciate your help. Have a nice day. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in | 6/11/2019 | 6/12/2019 | 6/12/2019 | A | PART |
Jim Page
|
|
|
Partial rough to cover inspection for attic dry system complete, notated city approved drawings with yellow highlighter areas approved for cover on the dry system.
Daniel Arce is the contact for this RTC inspection. He is requesting it to be done on the dry system. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Conference | 6/3/2019 | 6/5/2019 | 6/5/2019 | A | DONE |
Jim Page
|
|
|
Fire conference complete. Hardlids in level 2 bathrooms can be installed before tenting, will verify tenting is in place after other trades install is complete.
Colton Cox is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 5/17/2019 | 5/20/2019 | 5/20/2019 | P | PART |
Jim Page
|
|
|
Rough in inspection for Section A Phase 2 complete, notated city approved drawings with yellow highlighter areas approved for cover.
Colton Cox is the contact. This rough-in is for Section A Phase 2, and Colton would like it at 2PM if possible. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 5/10/2019 | 5/13/2019 | 5/13/2019 | P | PASS |
Jim Page
|
|
|
OK to cover area "A" only, notes made to plan mod #1 plan on site.***MAS**
Colton Cox is the contact. This rough-in is for section A of the building. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus
|
Plan assigned to (Stumbaugh) | 5/9/2019 | | 5/10/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 5/10/2019 | | 5/10/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/10/2019 | | DONE |
Mark Stumbaugh
|
|
|
Plan Mod Fee $150.00
|
Permit Ready to Issue | | | 5/10/2019 | | DONE |
|
|
|
plan mod ready-do not re issue
|
CHANGE STATUS TO (ISS) | | | 5/10/2019 | | DONE |
|
|
|
plan mod
|
Plan Modification Accepted | | | 5/9/2019 | | DONE |
|
|
|
plan mod started in e plan-changing pipe routing-assigned to MAS
|
Issue and Print Permit | | | 5/1/2019 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/29/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 4/29/2019 | | 4/29/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 4/29/2019 | | 4/29/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/29/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 4/29/2019 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/23/2019 | | 4/26/2019 | | FAIL |
Mark Stumbaugh
|
|
|
|
Intake Approval | | | 4/23/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 4/23/2019 | | 4/23/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Application received | | | 4/15/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 15 2019 11:02AM
|