Permit Information
Permit NumberFIR19-00268
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION
Site Address 333 N 1ST ST
Project NameSLHS DCIP Surgery Center
Customer Number 
ePlanReviewYes
Description
Provide a new fire alarm system in an existing building remodel. Design of the surgery center includes 100% smoke coverage. Smoke fire dampers are to be activated by full area detection in the surgery center and by in duct detection for remaining areas, magnetic door holders are activated by corridor area coverage in the surgery center and do not require centered detectors within five feet. The remaining floors / areas have corridors that do not have full coverage and are activated by dedicated detectors at door holders. System includes manual alarm stations at all exits and several nurse’s stations, duct detection with HVAC interface, elevator recall and shunt. Notification is to be public mode. This work is associated with building permit BLD18-03657.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/27/201912/3/201912/3/2019APASS
DetailsJim Page
Final fire alarm inspection is complete.

6am per Joe Bruce // Damien Phone #: ###-####
Fees Due Hold11/27/2019 11/27/2019 DONE
Details
INSP-Final Inspection11/26/201911/26/201911/26/2019AFAIL
DetailsJim Page
Fire alarm has audio issues with the three temporal, a re-inspection will be required after audio issue is resolved.

###-#### - Damien
CHANGE STATUS TO (ISS)  11/21/2019 DONE
Plan resubmittals received  11/19/2019 DONE
3rd as built per Kristian -location moves
Plan assigned to (Lee)11/19/2019 11/19/2019 DONE
DetailsLee G Meredith
4th as built per Kristian -location moves
1st review completed  11/19/2019 DONE
Alarm Plan Check11/19/2019 11/19/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  11/19/2019 DONE
Plan mod passed. $65.00 one hour minimum review fee due.
Permit Ready to Issue  11/19/2019 DONE
Plan mod approved
INSP-Final Inspection11/13/201911/14/201911/14/2019AFAIL
DetailsJim Page
City approved drawings have been notated areas that need to be corrected. Relocate dcevices that are overspaced or adjust candella setting. Provide weather proof devices in restrooms that have showers. Add notication in multi-person offices as dicussed.

5am
Fees Due Hold11/13/2019 11/13/2019 DONE
Details
INSP-Final Inspection11/7/201911/7/201911/7/2019PPART
DetailsJim Page
Fire alarm inspection for surgical suite, southwest side of building complete to include corridors outside of surgical suite. Remaining areas to be inspected at a later date.

Phone #: ###-#### Inspection requested via web by Kristin Dolan
Plan resubmittals received  11/4/2019 DONE
Lauren called to have the workflow opened for as builts #2
Plan assigned to (Lee)11/4/2019 11/4/2019 DONE
DetailsLee G Meredith
as built
1st review completed  11/4/2019 DONE
Alarm Plan Check11/4/2019 11/4/2019 PASS
DetailsLee G Meredith
Plan Modification Accepted  11/4/2019 DONE
PLANS TAKEN FRONT DESK ALARM  11/4/2019 DONE
Plan mod passed. Minimum review fee of $65 is due.
Permit Ready to Issue  11/4/2019 DONE
DO NOT ISSUE -Plan mod approved
CHANGE STATUS TO (ISS)  11/4/2019 DONE
PLAN MOD
Fees Due Hold10/25/2019 10/25/2019 DONE
Details
INSP-Final Inspection10/24/201910/24/201910/24/2019PFAIL
DetailsJim Page
Relocate smoke detectors that are to close to HVAC registers. Provide weather proof A/V devides in prep area behind surgical suites. Verify if door hold magnets are going to stay in place, if door holds stay then smoke detectors will be required for door release.

Phone #: ###-#### Inspection requested via web by Kristin Dolan
INSP-Final Inspection10/22/201910/23/201910/23/2019AFAIL
DetailsJim Page
Occupancy is a B occupancy, provide notification in post op and pre op rooms. Relocate notification in areas as discussed. No devices tested.

Call ahead to Damien @ ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan
Plan assigned to (Lee)10/21/2019 10/22/2019 DONE
DetailsLee G Meredith
as built
Intake Approval  10/22/2019 PASS
1st review completed  10/22/2019 PASS
Alarm Plan Check10/22/2019 10/22/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/22/2019 DONE
As built - No fee
Permit Ready to Issue  10/22/2019 DONE
as built approved
CHANGE STATUS TO (ISS)  10/22/2019 DONE
Plan resubmittals received  10/21/2019 DONE
start as built workflow per Kristin at Johnson Controls
Telephone call  9/25/2019 DONE
Received a call from the architect at Hummel. He said that he had discussed the requirements of interfacing the fire alarm system to the elevator in question with Gary Barnes. Gary informed him that due to the age and length of travel, interface will not be required.
Meeting  9/19/2019 DONE
Met with GC regarding elevator recall. He indicated that one of the existing elevators was not capable of recall and wanted direction on how to accomplish shunt. I informed him that shunt cannot be installed if elevator is not capable of full recall. Told him to contact Gary Barnes from the state elevator inspectors office for direction.
Plan resubmittals received  5/2/2019 DONE
1st review completed  5/2/2019 PASS
Alarm Plan Check5/2/2019 5/2/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  5/2/2019 DONE
Passed with requirements noted on drawings.
Permit Ready to Issue  5/2/2019 DONE
met
Issue and Print Permit  5/2/2019 DONE
Plan assigned to (Lee)4/23/2019 4/24/2019 DONE
DetailsLee G Meredith
Plan resubmittals received  4/24/2019 DONE
1st review completed  4/24/2019 FAIL
All plans resubmitted with incorrect file name. Returned again to applicant for correction. New files were deleted and applicant was emailed correction requirements.
Application received  4/16/2019 DONE
Application submitted via PDS Online on Apr 16 2019 11:56AM