Permit NumberFIR19-00269
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1208 E SHAW MOUNTAIN RD
Project NameMatt & Jill Minor Residence
Customer Number 
ePlanReviewYes
Description
TVFP will install a complete automatic wet pipe fire sprinkler system throughout the new building per NFPA 13D. Work will begin at the connection to the 2" fire stub at the property line and extend 80' of 2" poly to the mechanical room in the basement. The system has been hydraulically calculated 10' height ceilings.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/28/201910/28/201910/28/2019PPASS
DetailsJim Page
Previouly noted items have bee corrected, head box not required per NFPA 13D, section 5.1.1.2, final fire sprinkler inspection is complete.

Please call Troy Nelson for inspection time. Currently the bell is working. Phone #: ###-#### Inspection requested via web by Daniel Buccino
INSP-Final Inspection9/30/20199/30/20199/30/2019PFAIL
DetailsJim Page
Provide head box with head wrench and correct number of spare heads. Circuit breaker for flow switch tripped with flow switch activation, could not get bell to operate, bell operation will need to be repaired.

Adam Phone #: ###-####
INSP-Final Inspection9/11/20199/11/20199/11/2019PCANC
DetailsTroy Cobbley
Could not perform inspection due to time constraints. Please call troy with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
INSP-Sprinkler Rough-in5/22/20195/23/20195/23/2019APASS
DetailsJim Page
All tenting in place at time of inspection, cover for overhead fire sprinkler piping approved, sticker for cover approvel placed on window with other trade associated stickers.

This a rough-in inspection for tenting. Phone #: ###-#### Inspection requested via web by Daniel Buccino
INSP-Sprinkler Rough-in5/20/20195/20/20195/20/2019PPART
DetailsJim Page
Rough in inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping located between conditioned spaces approved for cover, piping requiring tenting to be inspected at a later date. Piping requiring tenting not approved for cover.

Please call Lonnie with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
Issue and Print Permit  4/17/2019 DONE
Application received  4/16/2019 DONE
Application submitted via PDS Online on Apr 16 2019 12:47PM
Intake Approval  4/16/2019 PASS
DetailsMark Stumbaugh
Plan assigned to (Stumbaugh)4/16/2019 4/16/2019 DONE
DetailsMark Stumbaugh
Sprinkler Plan Check4/16/2019 4/16/2019 PASS
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  4/16/2019 DONE
DetailsMark Stumbaugh
Permit Ready to Issue  4/16/2019 DONE
met