INSP-Final Inspection | 5/22/2019 | 5/22/2019 | 5/22/2019 | P | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, final fire sprinkler inspection for area of work complete.
Adam Phone #: ###-####
|
INSP-Final Inspection | 5/20/2019 | 5/21/2019 | 5/21/2019 | A | FAIL |
Jim Page
|
|
|
Fire sprinkler head in changing room has paint on the seat, head will need to be replaced. Texture mud needs to be cut around the other 2 heads in changing room, heads to not have escutcheons installed due to drywall mud issue.
Adam Chitwood To coinside with the fire life safety final. Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
INSP-Final Inspection | 5/20/2019 | 5/21/2019 | 5/20/2019 | P | CANC |
Jim Page
|
|
|
Adam Chitwood To coinside with the fire life safety final Phone #: ###-#### >> Inspection requested via web by Brodie Stenquist Inspection cancelled from web by: Brodie Stenquist
|
INSP-Sprinkler Rough-in | 5/1/2019 | 5/1/2019 | 5/1/2019 | P | PASS |
Troy Cobbley
|
|
|
Rough-in passed. Piping can be covered.
Adam Phone #: ###-####
|
Intake Approval | | | 4/24/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 4/24/2019 | | 4/24/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 4/24/2019 | | 4/24/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/24/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 4/24/2019 | | DONE |
|
|
|
met
|
Issue and Print Permit | | | 4/24/2019 | | DONE |
|
|
|
|
Application received | | | 4/23/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 23 2019 4:14PM
|