Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR19-00293
StatusFinaled
Name PROTEX
Site Address 5450 W GOWEN RD
Project NameKnife River Shop/Office
Customer Number 
ePlanReviewYes
Description
Add new fire panel to new construction for sprinkler monitoring and elevator recall. This work is associated with building permit BLD19-00101.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/18/201912/18/201912/18/2019PPASS
DetailsTroy Cobbley
Permit finaled.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection12/17/201912/17/201912/17/2019PCANC
DetailsTroy Cobbley
Phone lines have been cut. Inspection requested via web by Morgan Ahten
Plan Modification Accepted  12/17/2019 DONE
as built per Morgan - panel change
Plan assigned to (Lee)12/17/2019 12/17/2019 DONE
DetailsLee G Meredith
as built per Morgan - panel change
1st review completed  12/17/2019 DONE
Alarm Plan Check12/17/2019 12/17/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/17/2019 DONE
As built - No Fee
CHANGE STATUS TO (ISS)  12/17/2019 DONE
as built no fee
INSP-Alarm Testing12/10/201912/11/201912/11/2019ADONE
DetailsTroy Cobbley
Head end equipment and interconnection with the fire sprinkler devices tested. For a final sign off we need the phone line troubles to report in less than 200 seconds, need elevator recall tested and final documents. Knox box needs installed as well.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Alarm Testing12/10/201912/10/201912/10/2019PFAIL
DetailsTroy Cobbley
We were unable to test phone lines due to non-functioning testing equipment. Inspection stopped since I can not verify communication means.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan assigned to (Lee)4/25/2019 4/25/2019 DONE
DetailsLee G Meredith
Miscellaneous action  4/25/2019 DONE
Emailed Morgan to let him know that elevator controllers located in the shaft still need smoke detection and suggested he contact state inspector Gary Barnes to determint the best location.
1st review completed  4/25/2019 PASS
Alarm Plan Check4/25/2019 4/25/2019 PASS
DetailsLee G Meredith
Passed as noted.
PLANS TAKEN FRONT DESK ALARM  4/25/2019 DONE
Passed as noted on drawings.
Permit Ready to Issue  4/25/2019 DONE
Issue and Print Permit  4/25/2019 DONE
Application received  4/24/2019 DONE
Application submitted via PDS Online on Apr 24 2019 3:00PM