INSP-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 10/10/2019 | 10/11/2019 | 10/11/2019 | A | FAIL |
Troy Cobbley
|
|
|
Tested the induct detectors. Notification needs to acivate for entire building when an alarm condition is present. It currently does not. Need to test the smoke detectors with the hvac units in heat mode to verify correct shut down. Kristen Phone #: ###-####
|
Permit Ready to Issue | | | 10/8/2019 | | DONE |
|
|
|
as built approved
|
CHANGE STATUS TO (ISS) | | | 10/8/2019 | | DONE |
|
|
|
as built no fee per Lee change back to ISS
|
Plan resubmittals received | | | 10/7/2019 | | DONE |
|
|
|
as built
|
Plan assigned to (Lee) | 10/7/2019 | | 10/7/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 10/7/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 10/7/2019 | | 10/7/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 10/7/2019 | | DONE |
|
|
|
As built - No fee.
|
INSP-Final Inspection | 10/3/2019 | 10/4/2019 | 10/4/2019 | A | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for notification corrections that are needed. I also noted that the door magnets that have been installed at the main exit may need to be connected to the fire alarm system as per IFC chapter 10. This hospital is occupied and the test needs to be @ 7 am. Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
CHANGE STATUS TO (ISS) | | | 9/23/2019 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 7/9/2019 | | 9/20/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 9/20/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 9/20/2019 | | 9/20/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 9/20/2019 | | DONE |
|
|
|
Plan mod passed. No additional comments.
|
Permit Ready to Issue | | | 9/20/2019 | | DONE |
|
|
|
Plan mod approved -
DO NOT RE ISSUE
|
Plan Modification Accepted | | | 7/9/2019 | | DONE |
|
|
|
ADDED FIVE NOTIFICATION DEV.
REMOVING ROOM NURSE ADMIN 327
|
Issue and Print Permit | | | 6/27/2019 | | DONE |
|
|
|
|
Alarm Plan Check | 6/17/2019 | | 6/17/2019 | | PASS |
Lee G Meredith
|
|
|
|
Plan resubmittals received | | | 6/17/2019 | | DONE |
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/17/2019 | | DONE |
|
|
|
Passed with comments.
|
Permit Ready to Issue | | | 6/17/2019 | | DONE |
|
|
|
met
|
Application received | | | 5/14/2019 | | DONE |
|
|
|
Application submitted via PDS Online on May 14 2019 9:37AM
|
Plan assigned to (Lee) | 5/14/2019 | | 5/14/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 5/14/2019 | | FAIL |
|
|
|
Failed pre-screen review. Several common or shared areas appear to have inadequate visible notificaiton. Returned to applicant for corrections.
|