Permit Information
Permit NumberFIR19-00378
StatusFinaled
Name PROTEX
Site Address 2800 S MAPLE GROVE RD
Project NameMaple Grove Upgrade
Customer Number 
ePlanReviewYes
Description
Replace existing fire alarm system with voice system. This work does not appear to be associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/16/20198/16/20198/16/2019PPASS
DetailsMark Scharfen
Tested and verified smokes/pulls and duct detectors. All speaker strobes functioned correctly. There is no hood installed in kitchen so point will need to be deleted off print and sent in as as build.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
CHANGE STATUS TO (ISS)  8/16/2019 DONE
Plan resubmittals received  8/15/2019 DONE
as built per Morgan
Plan assigned to (Lee)8/15/2019 8/15/2019 DONE
DetailsLee G Meredith
1st review completed  8/15/2019 PASS
Alarm Plan Check8/15/2019 8/15/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/15/2019 DONE
Plan mod approved.
Permit Ready to Issue  8/15/2019 DONE
CHANGE STATUS TO (ISS)  8/15/2019 DONE
AS BUILT
Permit Ready to Issue  8/15/2019 DONE
THERE ARE FEES
Telephone call  8/15/2019 DONE
SPOKE WITH ROB INFORMING HIM THAT THERE ARE PLAN MOD FEES NEEDING TO BE PAID
INSP-Final Inspection8/13/20198/13/20198/13/2019PFAIL
DetailsTroy Cobbley
Plan modifications are needed showing all changes. Strobes need to be added in the large boys and girls restrooms and in all classrooms with the partial height walls. We set off the notification and I could not see a reasonable effect of the strobe mounted in the center of the room. Most of the areas checked there was no effect seen. Notification devices have been added to rooms, not all rooms are shown on the plans, smoke detectors are over spaced in three locations at the front lobby, fire smoke dampers are shown on the plans. Some strobes are blocked (kitchen), some are overspaced off walls and some 15cd exceed the 10' max ceiling height allowance. Also this inspection/permit sign off needs to follow the other FIR for the head end equipment sign off. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan Modification Accepted  8/12/2019 DONE
as built requested by Morgan from Protex
Plan assigned to (Lee)8/12/2019 8/12/2019 DONE
DetailsLee G Meredith
as built
Fees Paid/Begin Review  8/12/2019 PASS
Alarm Plan Check8/12/2019 8/12/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/12/2019 DONE
As built passed. No fee.
Permit Ready to Issue  8/12/2019 DONE
CHANGE STATUS TO (ISS)  8/12/2019 DONE
as built per lee
INSP-Final Inspection8/9/20198/9/20198/9/2019PFAIL
DetailsJim Page
Noted defecincies in multi purpose room located by the kitchen and in the kitchen area on city approved drawings, stopped inspection at kitchen due too the number of defecincies, notated issues that were inspected on the city approved drawing.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection8/8/20198/8/20198/8/2019PCANC
DetailsTroy Cobbley
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
INSP-Final Inspection8/5/20198/5/20198/5/2019PCANC
DetailsTroy Cobbley
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
Plan assigned to (Lee)7/25/2019 7/26/2019 DONE
DetailsLee G Meredith
plan mod
1st review completed  7/26/2019 PASS
Alarm Plan Check7/26/2019 7/26/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  7/26/2019 DONE
As Built - No Fee
Permit Ready to Issue  7/26/2019 DONE
CHANGE STATUS TO (ISS)  7/26/2019 DONE
Plan Modification Accepted  7/25/2019 DONE
per Morgan-start plan mod for as builts-assigned to Lee M
Plan assigned to (Lee)6/3/2019 6/3/2019 DONE
DetailsLee G Meredith
1st review completed  6/3/2019 PASS
Alarm Plan Check6/3/2019 6/3/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/3/2019 DONE
Passed as noted on drawings.
Permit Ready to Issue  6/3/2019 DONE
met
Issue and Print Permit  6/3/2019 DONE
Application received  5/30/2019 DONE
Application submitted via PDS Online on May 30 2019 10:56AM