Permit Information
Permit NumberFIR19-00445
StatusFinaled
Name PROTEX
Site Address 2015 N CURTIS RD
Project NameKoelsch Cafeteria Bldg.
Customer Number 
ePlanReviewYes
Description
Add Voice Fire Alarm Panel panel to new cafeteria building. This work is associated with BLD18-04112.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/16/201910/17/201910/17/2019APASS
DetailsTroy Cobbley
Permit finaled.

Contact is Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan Modification Accepted  10/15/2019 DONE
as built per morgan with protex
Plan assigned to (Lee)10/15/2019 10/15/2019 DONE
DetailsLee G Meredith
Intake Approval  10/15/2019 PASS
1st review completed  10/15/2019 PASS
Alarm Plan Check10/15/2019 10/15/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/15/2019 DONE
As built - No fee.
Permit Ready to Issue  10/15/2019 DONE
CHANGE STATUS TO (ISS)  10/15/2019 DONE
as built
INSP-Final Inspection10/14/201910/14/201910/14/2019PFAIL
DetailsTroy Cobbley
Need as-builts showing the candella change and the added duct smoke detector. Contact is Dirk. Client requests final for after school hours. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan assigned to (Lee)10/3/2019 10/10/2019 DONE
DetailsLee G Meredith
Intake Approval  10/10/2019 PASS
1st review completed  10/10/2019 PASS
Alarm Plan Check10/10/2019 10/10/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/10/2019 DONE
As built - No fee.
Permit Ready to Issue  10/10/2019 DONE
As built approved
CHANGE STATUS TO (ISS)  10/10/2019 DONE
INSP-Final Inspection10/2/201910/3/201910/3/2019PFAIL
DetailsTroy Cobbley
Ceiling mounted strobes are overspaced in the Kitchen. Inspection stopped. Devices need to be relocated or candellas adjusted. The fire alam plans need to be reviewed by the engineer of record prior to plan review approval. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan resubmittals received  10/3/2019 DONE
Morgan with Protex required for the workflow to be opened for as builts
Application received  6/17/2019 DONE
Application submitted via PDS Online on Jun 17 2019 11:57AM
Plan assigned to (Lee)6/17/2019 6/17/2019 DONE
DetailsLee G Meredith
1st review completed  6/17/2019 PASS
Alarm Plan Check6/17/2019 6/17/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/17/2019 DONE
Passed with review comments and drawing notes.
Permit Ready to Issue  6/17/2019 DONE
Issue and Print Permit  6/17/2019 DONE