Permit Information
Permit NumberFIR19-00452
StatusFinaled
Name ALL VALLEY FIRE INSPECTIONS AND SER
Site Address 3390 N COLLISTER DR
Project NameThe Cottage New Fire Alarm
Customer Number 
ePlanReviewYes
Description
Scope of Work: Install new fire alarm. Relocate existing dialer to new FA. Low Frequency sounder bases are to be installed in the 15 resident rooms. 110 Candela strobes are to be installed in the 15 resident rooms at 25 inches below ceiling to top of strobe. The HVAC system is dedicated to PODs and none are over 2000cfm. Door holds to be re-used. All new wiring to be free-hung in attic using fire wire. The facilty is staffed 24/7/365.
This work does not appear to be associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/15/201910/17/201910/17/2019APASS
DetailsTroy Cobbley
Permit finaled. Previous corrections addressed.

Phone #: ###-#### Inspection requested via web by Jason Heath
INSP-Final Inspection10/10/201910/11/201910/11/2019PFAIL
DetailsJim Page
Audio visual devices in restrooms did not function. Smoke detector in room 6 is within 36 inches of HVAC register, relocate detector as discussed.

Phone #: ###-#### Inspection requested via web by Jason Heath
Plan resubmittals received  10/10/2019 DONE
Intake Approval  10/10/2019 PASS
1st review completed  10/10/2019 PASS
Alarm Plan Check10/10/2019 10/10/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/10/2019 DONE
As built - No fee.
Permit Ready to Issue  10/10/2019 DONE
CHANGE STATUS TO (ISS)  10/10/2019 DONE
Plan resubmittals received  10/9/2019 DONE
as built per Jason-started workflow in e plan
Plan assigned to (Lee)10/9/2019 10/9/2019 DONE
DetailsLee G Meredith
as built per Jason Heath

Returned to jason for file name correction.
Plan assigned to (Lee)6/17/2019 6/18/2019 DONE
DetailsLee G Meredith
1st review completed  6/18/2019 PASS
Alarm Plan Check6/17/2019 6/18/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/18/2019 DONE
Passed with requirements.
Permit Ready to Issue  6/18/2019 DONE
met
Issue and Print Permit  6/18/2019 DONE
Application received  6/17/2019 DONE
Application submitted via PDS Online on Jun 17 2019 1:53PM