Permit NumberFIR19-00461
StatusIssued
Name JOHNSON CONTROLS FIRE PROTECTION
Site Address 2121 N COLE RD
Project NameFairmont Jr High Kitchen Cafe
Customer Number 
ePlanReviewYes
Description
Fairmont Jr High Kitchen Cafe - Renovations to add new classrooms in existing areas of gym, and cafeteria. New areas will require CO detection in classrooms, smoke detection in the hallway, and new notification installed in areas of work based on ADA compliance. Providing In -Duct Detectors and IAM's for Smoke Damper on HVAC system. Johnson Controls will provide as build drawings for this project prior to submittal to Boise Fire to its contractors for reference. This work is associated with BLD19-00228.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
CHANGE STATUS TO (ISS)  9/5/2019 DONE
per troy only partial pass
INSP-Final Inspection9/3/20199/4/20199/4/2019APART
DetailsTroy Cobbley
A temporary for this permit is being given until an upgrade agreement has been finalized with the Boise Fire Dept for the fire alarm system.

This inspection needs to be before 7:30 am as this is a school and they will be in session. Please call ahead to Brian @ ###-####. Phone #: ###-#### Inspection requested via web by Kristin Dolan
INSP-Final Inspection8/29/20198/30/20198/30/2019AFAIL
DetailsTroy Cobbley
FIre smoke damper did not function when smoke detector activated. Both dampers will need to be tested. Per Boise Fire a temp for fire alarm will be ok, when dampers function, until the fire alarm upgrade agreement is finalized. Phone #: ###-#### Inspection requested via web by Kristin Dolan
Plan resubmittals received  8/19/2019 DONE
Alarm Plan Check8/19/2019 8/19/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/19/2019 DONE
As built - No fee.
Permit Ready to Issue  8/19/2019 DONE
per Lee M no as built fee
CHANGE STATUS TO (ISS)  8/19/2019 DONE
per Lee M no as built fee
INSP-Final Inspection8/16/20198/16/20198/16/2019PFAIL
DetailsMark Scharfen
CO/Supervisory monitoring is not tied into AES, has not been pretested. Had conversation with technician. Will need to be scheduled after system has been properrly pretested.

end of day inspection if possible. please call ahead to coordinate. Phone #: ###-#### Inspection requested via web by Kristin Dolan
Plan resubmittals received  8/16/2019 DONE
request to open for as built by Kristen from Johnson Control
Plan assigned to (Lee)8/16/2019 8/16/2019 DONE
DetailsLee G Meredith
as built
1st review completed  8/16/2019 FAIL
Previously noted item that required correction has not been addressed. CO alarm is to report to the monitoring station as an alarm. It still shows as a supervisory on the drawings.
INSP-Final Inspection8/12/20198/14/20198/14/2019PCANC
DetailsMark Scharfen
Last call of the day if possible. Phone #: ###-#### >> Inspection requested via web by Kristin Dolan Inspection cancelled from web by: Kristin Dolan
Issue and Print Permit  6/27/2019 DONE
Plan assigned to (Lee)6/19/2019 6/20/2019 DONE
DetailsLee G Meredith
1st review completed  6/20/2019 PASS
Alarm Plan Check6/20/2019 6/20/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/20/2019 DONE
Passed with commnets.
Permit Ready to Issue  6/20/2019 DONE
met
Application received  6/19/2019 DONE
Application submitted via PDS Online on Jun 19 2019 12:34PM