Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR19-00475
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 800 W MAIN ST Unit: 1200
Project NameGardner Company Office T.I.
Customer Number 
ePlanReviewYes
Description
Shilo will add, relocate, replace with new both upright and pendent sprinklers to accommodate the new wall and ceiling layout on the 12th Floor of 8th and Main Tower for the new Gardner Office.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/9/201910/9/201910/9/2019PPASS
DetailsJim Page
Previously noted items have been corrected, final fire sprinkler inspection for area of work complete.

Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection10/3/201910/7/201910/7/2019AFAIL
DetailsTroy Cobbley
Still need to remove the tape from the heads.

Jon Beazer is the contact. It doesn''t matter what time of day this inspection takes place. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in9/10/20199/11/20199/11/2019AFAIL
DetailsTroy Cobbley
Remove tape from heads, in a southwest office it appears a new upright head is blocked by round duct, in a northwest office a pendant head exceeds 9'-0" from a wall, an upright head needs to be added as per plans above a cloud ceiling assembly as marked on the plans.

Jon Beazer is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
Application received  6/25/2019 DONE
Application submitted via PDS Online on Jun 25 2019 1:59PM
Intake Approval  6/25/2019 PASS
DetailsMark Stumbaugh
Plan assigned to (Stumbaugh)6/25/2019 6/25/2019 DONE
DetailsMark Stumbaugh
Sprinkler Plan Check6/25/2019 6/25/2019 PASS
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  6/25/2019 DONE
DetailsMark Stumbaugh
Permit Ready to Issue  6/25/2019 DONE
Issue and Print Permit  6/25/2019 DONE