INSP-Final Inspection | 8/23/2019 | 8/23/2019 | 8/23/2019 | P | PASS |
Jim Page
|
|
|
Final fire alarm inspection complete.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
CHANGE STATUS TO (ISS) | | | 8/23/2019 | | DONE |
|
|
|
plan mod paid
|
Plan resubmittals received | | | 8/22/2019 | | DONE |
|
|
|
as built
|
Plan assigned to (Lee) | 8/22/2019 | | 8/22/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 8/22/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 8/22/2019 | | 8/22/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 8/22/2019 | | DONE |
|
|
|
Plan mod passed. No additional review comments.
|
Permit Ready to Issue | | | 8/22/2019 | | DONE |
|
|
|
plan mod
|
INSP-Final Inspection | 8/21/2019 | 8/21/2019 | 8/21/2019 | P | FAIL |
Jim Page
|
|
|
Notated city approved drawinsg where speaker strobes were overspaced/missing and smoke detection that was overspaced.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
Permit Ready to Issue | | | 8/21/2019 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 8/21/2019 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 8/19/2019 | | 8/20/2019 | | DONE |
Lee G Meredith
|
|
|
plan mod
|
Alarm Plan Check | 8/20/2019 | | 8/20/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 8/20/2019 | | DONE |
|
|
|
Plan mod passed. No additional comments.
|
Permit Ready to Issue | | | 8/20/2019 | | DONE |
|
|
|
DO NOT ISSUE plan mod accepted
|
Plan Modification Accepted | | | 8/19/2019 | | DONE |
|
|
|
as per Morgan-start plan mod
|
Plan resubmittals received | | | 7/17/2019 | | DONE |
|
|
|
|
Alarm Plan Check | 7/17/2019 | | 7/17/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/17/2019 | | DONE |
|
|
|
Passed with drawing notes and review comments.
|
Permit Ready to Issue | | | 7/17/2019 | | DONE |
|
|
|
met
|
Issue and Print Permit | | | 7/17/2019 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 6/26/2019 | | 6/26/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 6/26/2019 | | FAIL |
|
|
|
See notes on drawings. Make correcitons and resubmit.
|
CHANGE STATUS TO (REV) | | | 6/26/2019 | | DONE |
|
|
|
Changed back to REV due to corrections that need to be made.
|
Application received | | | 6/25/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 25 2019 3:20PM
|