Permit Information
Permit NumberFIR19-00478
StatusFinaled
Name STATE FIRE SALES & SERVICES
Site Address 9976 W PATTIE DR
Project NameBrooklyn House
Customer Number 
ePlanReviewYes
Description
Retrofit residence with NFPA 13D fire sprinkler system for occupancy as assisted living facility
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/9/20199/10/20199/11/2019PPASS
DetailsTroy Cobbley
Permit finaled.

All of the bent piping appears to meet NFPA 13 6.3.8. Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
INSP-Sprinkler Rough-in9/9/20199/10/20199/10/2019APART
DetailsTroy Cobbley
The deflector distance from the ceiling has been corrected but the hydro test failed due to visible leakage. Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
INSP-Sprinkler Rough-in9/6/20199/9/20199/9/2019AFAIL
DetailsTroy Cobbley
Corrections have been made except for the minimum destance from the sidewall deflector to the ceiling. Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
Plan assigned to (Stumbaugh)9/3/2019 9/4/2019 DONE
DetailsMark Stumbaugh
Sprinkler Plan Check9/4/2019 9/4/2019 PASS
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  9/4/2019 DONE
DetailsMark Stumbaugh
Permit Ready to Issue  9/4/2019 DONE
Plan Mod Approved
CHANGE STATUS TO (ISS)  9/4/2019 DONE
plan mod
Plan Modification Accepted  9/3/2019 DONE
Per Hunter, plan modification for 2 heads have been added
3 heads have been changed from sidewall to pendant configuration
walls have been changed to reflect renovations
piping has been rerouted to reflect field conditions.
The riser has been moved a few feet along the wall it was previously mounted on.
The system has been recalculated to reflect these changes.
INSP-Sprinkler Rough-in8/29/20198/29/20198/29/2019PFAIL
DetailsTroy Cobbley
As-builts or plan mods are needed showing the piping routing changes (additional fittings), per the data sheet for the sidewall heads the min. mounting distance from the ceiling 4" but the heads have been installed at 3 1/2". Also the sidewall heads have a max distance to be mounted off a wall and that has been exceeded. Verification needs to be provided that shows the heads have been installed per their listing. I noted the center line in the garage has no wall behind the sidewall heads again is this listed. I will need verification from the state that sprinkler coverage is not needed in the closet close to the riser. I will need to see the tenting where the piping passes above the Kitchen cabinets. I have not looked at any of the fire pump/tank items. Contact: Ricky Sullivan Phone #: ###-#### Inspection requested via web by Hunter Fillmore
Sprinkler Plan Check6/27/2019 6/28/2019 PASS
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  6/28/2019 DONE
DetailsMark Stumbaugh
Permit Ready to Issue  6/28/2019 DONE
Issue and Print Permit  6/28/2019 DONE
Application received  6/27/2019 DONE
Application submitted via PDS Online on Jun 27 2019 3:09PM
Intake Approval  6/27/2019 PASS
DetailsMark Stumbaugh
Plan assigned to (Stumbaugh)6/27/2019 6/27/2019 DONE
DetailsMark Stumbaugh