Permit Information
Permit NumberFIR19-00482
StatusFinaled
Name M2 AUTOMATION
Site Address 7499 W OVERLAND RD
Project NameHampton Inn Boise Spectrum
Customer Number 
ePlanReviewYes
Description
Minor fire alarm modification required due to building permit BLD18-03923 changes. This work is associated with building permit BLD18-03923.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/13/20198/13/20198/13/2019PPASS
DetailsTroy Cobbley
Permit finaled. Sync issue has been approved by Boise Fire.

Thanks Troy Have a terrific day. Phone #: ###-#### Inspection requested via web by Michael Timmerman
INSP-Alarm Testing8/12/20198/13/20198/13/2019APASS
DetailsTroy Cobbley
Permit finaled as per Boise Fire.

Hi Troy. Chief Johnson is going to let the synchronization slide for now. any future TIs in this location will more than likely require Hampton to Upgrade their fire alarm system. Let me know if this is just a sign off on your end or if we need to meet on site. Thanks Mike Phone #: ###-#### Inspection requested via web by Michael Timmerman
INSP-Alarm Testing7/31/20198/1/20198/1/2019PDONE
DetailsTroy Cobbley
I met mike and witnessed the notification changes mike had made. I can still hear the two different horn temporal rythms from either side of the walls. I let cheif Ron know of my findings.

Michael Phone #: ###-####
Permit Ready to Issue  7/31/2019 DONE
CHANGE STATUS TO (ISS)  7/31/2019 DONE
1st review completed  7/31/2019 PASS
Alarm Plan Check7/31/2019 7/31/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  7/31/2019 DONE
As built - No fee.
CHANGE STATUS TO (ISS)  7/31/2019 DONE
this was not put in ISS status after as built
Plan assigned to (Lee)7/25/2019 7/31/2019 DONE
DetailsLee G Meredith
as built
INSP-Alarm Testing7/24/20197/25/20197/25/2019PFAIL
DetailsTroy Cobbley
The notification (horns) did not sync as required per NFPA 72 18.4.2.4. Need as-builts approved. Thanks for coming out yesterday Troy. I apologize for the inefficiency. I (We) know better than to waist your time. Learned something new about the spare Simplex NAC output used as a trigger. Call me when you feel you can make it. Thanks Mike
Phone #: ###-#### Inspection requested via web by Michael Timmerman
Plan resubmittals received  7/25/2019 DONE
as built per Michae at M2 Automation
INSP-Final Inspection7/24/20197/24/20197/24/2019PFAIL
DetailsTroy Cobbley
The new notification circuit is not working.

Hi Troy This is the Hampton Inn Spectrum Hotel. I will call you this morning to set up an inspection this afternoon. Thanks Mike Timmerman. Phone #: ###-#### Inspection requested via web by Michael Timmerman
Plan assigned to (Lee)6/28/2019 7/1/2019 DONE
DetailsLee G Meredith
1st review completed  7/1/2019 PASS
Alarm Plan Check7/1/2019 7/1/2019 PASS
DetailsLee G Meredith
PLANS/APPL TAKEN TO FRONT DESK  7/1/2019 DONE
Passed with comments.
Permit Ready to Issue  7/1/2019 DONE
Met
Issue and Print Permit  7/1/2019 DONE
Application received  6/28/2019 DONE
Application submitted via PDS Online on Jun 28 2019 1:02PM