INSP-Final Inspection | 9/4/2019 | 9/4/2019 | 9/4/2019 | P | PASS |
Jim Page
|
|
|
Automatic shutoff valve for gas was installed backwards, not wiht the flow as indicated on the housing of valve. A new valve has been installed with the correct direction and gas shutoff happened with hood suppression system activation. Final inspection for hood suppression system complete.
|
INSP-Final Inspection | 9/3/2019 | 9/4/2019 | 9/4/2019 | A | FAIL |
Jim Page
|
|
|
Still have gas flowing after hood suppression system activation and gas valve automatic shutoff has been actuated.
Phone #: 2086157641 >> Inspection requested via mobile web by Richard Johnson
|
INSP-Final Inspection | 8/30/2019 | 9/3/2019 | 9/3/2019 | A | FAIL |
Jim Page
|
|
|
Relocate manual pull station to a code compliant location, cuurent location is less than 9 foot from corner edge of hood.
Phone #: 2086157641 >> Inspection requested via mobile web by Richard Johnson
|