Information based on query as of Thursday, June 27, 2024.
Permit Information
Permit NumberFIR19-00536
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 3650 S MILLBROOK WAY
Project NameBarnyard Daycare
Customer Number 
ePlanReviewYes
Description
Install new wet pipe sprinkler system in new daycare. Above, and below ceilings. Aboveground
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/20/201911/21/201911/21/2019PPASS
DetailsJim Page
Final fire sprinkler inspection is complete.

Cameron Phone #: ###-#### Inspection requested via web by Jeanine Halbesleben
INSP-Sprinkler Rough-in11/8/201911/8/201911/8/2019PPASS
DetailsJim Page
Rough to cover inspection for east and west corridors and kitchen area complete, heads have been added in the combustible concealed spaces as discussed, approved for cover.
INSP-Sprinkler Rough-in/Hydro11/8/201911/8/201911/8/2019PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

John Phone #: ###-####
INSP-Sprinkler Rough-in10/21/201910/23/201910/23/2019APART
DetailsJim Page
Provide fire sprinklers above ceiling grid in areas where TGI's are installed due to more than 6 inches between ceiling grid and TGI's(kitchen area, east and west corridors), remaining areas approved for cover, TGI areas not approved for cover.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
INSP-Sprinkler Rough-in10/11/201910/11/201910/11/2019PPART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping in attic space complete, attic piping is approved for cover. A follow up inspection will be required for cover of pendant head piping.

Cameran Phone #: ###-####
INSP-Sprinkler Rough-in9/19/20199/20/20199/20/2019APART
DetailsJim Page
Partial rough to cover inspection for overhead fire sprinkler piping complete, notated city approved drawings with red ink areas approved for cover.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
INSP-Supply line flush7/30/20198/5/20198/5/2019ADONE
DetailsJim Page
Flush has been completed.

Flush with Suez at 10 am Phone #: ###-#### Inspection requested via web by Matthew Lewis
INSP-Supply line flush8/2/20198/2/20198/2/2019ADONE
DetailsJim Page
Underground main line flush complete.
Issue and Print Permit  7/25/2019 DONE
Sprinkler Plan Check7/23/2019 7/24/2019 PASS
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  7/24/2019 DONE
DetailsMark Stumbaugh
Permit Ready to Issue  7/24/2019 DONE
Plan resubmittals received  7/23/2019 FAIL
DetailsMark Stumbaugh
Plan resubmittals received  7/23/2019 PASS
DetailsMark Stumbaugh
Plan assigned to (Stumbaugh)7/23/2019 7/23/2019 DONE
DetailsMark Stumbaugh
Sprinkler Plan Check7/19/2019 7/22/2019 FAIL
DetailsMark Stumbaugh
Application received  7/19/2019 DONE
Application submitted via PDS Online on Jul 19 2019 11:04AM
Intake Approval  7/19/2019 PASS
DetailsMark Stumbaugh
Plan assigned to (Stumbaugh)7/19/2019 7/19/2019 DONE
DetailsMark Stumbaugh