INSP-Final Inspection | 11/13/2019 | 11/13/2019 | 11/13/2019 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection for area of work complete.
Contact Noemi Carrero ###-#### 30 min prior to Final Fire Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 9/24/2019 | 9/25/2019 | 9/25/2019 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, rough to cover inspection is complete, approved for cover.
Contact Noemi Carerro 208###-#### 30 min prior to RTC insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 9/23/2019 | 9/23/2019 | 9/23/2019 | P | FAIL |
Jim Page
|
|
|
Sidewalls above ceiling grid in classroom 101 are more than 12 foot off of wall, heads are overspaced. Hardlids have been installed before rough in inspection has been performed, cover has not been approved. Mechanical room 114 has heads installed under duct work, still need heads above duct work 1 to 6 inches from bottom of deck, no fire sprinkler heads above duct work.
Contact Hunter Anderson ###-#### 30 min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
Plan resubmittals received | | | 8/13/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 8/13/2019 | | 8/13/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/13/2019 | | DONE |
Mark Stumbaugh
|
|
|
Double Fee - Starting work before permit issuance.
|
Permit Ready to Issue | | | 8/13/2019 | | DONE |
|
|
|
met
|
Issue and Print Permit | | | 8/13/2019 | | DONE |
|
|
|
|
Sprinkler Plan Check | 8/6/2019 | | 8/7/2019 | | FAIL |
Mark Stumbaugh
|
|
|
|
Application received | | | 8/6/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 6 2019 1:59PM
|
Intake Approval | | | 8/6/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 8/6/2019 | | 8/6/2019 | | DONE |
Mark Stumbaugh
|
|
|
|