INSP-Final Inspection | 12/2/2019 | 12/3/2019 | 12/3/2019 | P | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, final fire sprinkler inspection is complete.
Please call James before heading out so he can meet you there! Thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Final Inspection | 11/19/2019 | 11/19/2019 | 11/19/2019 | A | FAIL |
Jim Page
|
|
|
Provide sigange for fire bell. Wiring for irrigation shutdown not installed correctly, irrigation will not shut down during waterflow.
Call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Final Inspection | 11/14/2019 | 11/15/2019 | 11/15/2019 | A | CANC |
Jim Page
|
|
|
Call before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
INSP-Sprinkler Rough-in | 9/4/2019 | 9/5/2019 | 9/5/2019 | A | PASS |
Jim Page
|
|
|
All tenting in place at time of inspection, overhead fire sprinkler piping approved for cover.
Tenting inspection Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in/Hydro | 8/30/2019 | 8/30/2019 | 8/30/2019 | A | PART |
Jim Page
|
|
|
Rough in inspection complete, no tenting in place at time of inspection, cover is approved for piping between conditioned spaces, piping in attic spaces that requires tenting is not approved for cover.
|
INSP-Sprinkler Rough-in/Hydro | 8/29/2019 | 8/30/2019 | 8/30/2019 | P | DONE |
Jim Page
|
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
Issue and Print Permit | | | 8/20/2019 | | DONE |
|
|
|
|
Sprinkler Plan Check | 8/13/2019 | | 8/15/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/15/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 8/15/2019 | | DONE |
|
|
|
|
Intake Approval | | | 8/13/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 8/13/2019 | | 8/13/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Application received | | | 8/9/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 9 2019 2:54PM
|