Permit Information
Permit NumberFIR19-00610
StatusFinaled
Name APEX INTEGRATED SECURITY SOLUTIONS
Site Address 1290 W MYRTLE ST Unit: 190
Project NamePivot KA TI Suite 190
Customer Number 
ePlanReviewYes
Description
Pivot KA TI work add notification devices to this new tenant improvement area. Add new NACPS02 panel utilizing 2 NACs circuits to feed the area of work.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/24/201910/25/201910/25/2019APASS
DetailsJim Page
Previously noted items have been corrected, final fire alarm inspection is complete.

Phone #: 208831311 >> Inspection requested via mobile web by Nathan Price
INSP-Final Inspection10/21/201910/22/201910/22/2019AFAIL
DetailsJim Page
Reloacte audio visual device tghat is blocked by ductwork. Mag locks on access control are not interfaced with fire alarm system, per IFC access controled mag lock doors must release on general fire alarm. Provide weather proof audio visual devices in restrooms, no header/lintel provided in shower area making it a seperate compartment. Provide A/V device in staff locker room as discussed.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Final Inspection10/18/201910/21/201910/21/2019PCANC
DetailsTroy Cobbley
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Monday, October 21, 2019.
INSP-Alarm Testing10/18/201910/18/201910/18/2019PCANC
DetailsJim Page
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Friday, October 18, 2019.
Plan assigned to (Lee)8/16/2019 8/16/2019 DONE
DetailsLee G Meredith
1st review completed  8/16/2019 PASS
As noted
Alarm Plan Check8/16/2019 8/16/2019 PASS
DetailsLee G Meredith
As noted.
PLANS TAKEN FRONT DESK ALARM  8/16/2019 DONE
Passed as noted with review comments.
Permit Ready to Issue  8/16/2019 DONE
met
Issue and Print Permit  8/16/2019 DONE
(F) Reprint permit  8/16/2019 DONE
Application received  8/15/2019 DONE
Application submitted via PDS Online on Aug 15 2019 3:38PM