Permit Information
Permit NumberFIR19-00643
StatusIssued
Name APEX INTEGRATED SECURITY SOLUTIONS
Site Address 3304 LAKEHARBOR
Project NameEdgewater Aps Bldg N Cellular
Customer Number 
ePlanReviewYes
Description
Edgewater Apt Bldg N Cellular Installation Work is to add a Cellular Communicator on Building N to replace existing phone connection. PLAN MOD 12-10-19: Replace existing fire alarm panel. This change requires the entire system to meet current code compliance. This work is not associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/11/201912/11/201912/11/2019PCANC
DetailsTroy Cobbley
Per note on the plans the existing fire alarm system will need to meet current code. I spoke to the contractor about the issue. No inspection performed.

Phone #: 4087506433 >> Inspection requested via mobile web by Josiah
Plan assigned to (Lee)12/9/2019 12/10/2019 DONE
DetailsLee G Meredith
Plan mod to replace existing fire alarm panel.
1st review completed  12/10/2019 DONE
Alarm Plan Check12/10/2019 12/10/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/10/2019 PASS
Quick permit plan modification approved, as noted on the fire alarm pland drawing. Minimum review fee of $65.00 due.

FACP replacement requires entire system to be brought up to current code compliance.
Permit Ready to Issue  12/10/2019 DONE
plan mod
CHANGE STATUS TO (ISS)  12/10/2019 DONE
Plan Modification Accepted  12/9/2019 DONE
start plan mod workflow per Dante Frassa at Apex Boise
INSP-Final Inspection12/4/201912/5/201912/5/2019AFAIL
DetailsTroy Cobbley
A plan modification is required showing the fire alarm panel that was installed previously without a permit.

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
INSP-Sprinkler Rough-in/Hydro12/4/201912/5/201912/4/2019ACANC
DetailsJim Page
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Wednesday, December 04, 2019.
INSP-Final Inspection11/15/201911/15/201911/15/2019PFAIL
DetailsJim Page
Manufactures specs for fire panel requires the panel to be in an environment conditioned between 32 degrees fahrenheit to 120 degrees fahrenheit, provide conditioning in fire panel enclosure as discussed, conditioning has been provided for communicator encloser, heat detectors can remain in current location.

As early as possible Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
Telephone call  10/24/2019 DONE
Josiah called to say that there are no spare zones to add the panel heat detector and wanted to know if the heat could be tied to a pull station zone. I informed him that if the pull stations are on floor by floor zones that he could put the heat on the same zone as the pull for that floor. Pull stations are currently the only alarm initiating devices so this should not create confusion.
INSP-Final Inspection10/16/201910/16/201910/16/2019PFAIL
DetailsTroy Cobbley
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
Plan assigned to (Lee)9/3/2019 9/3/2019 DONE
DetailsLee G Meredith
1st review completed  9/3/2019 PASS
Alarm Plan Check9/3/2019 9/3/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/3/2019 DONE
Quick permit passed. No comments.
Override - Parcel Holds  9/3/2019  
Permit Ready to Issue  9/3/2019 DONE
MET
Issue and Print Permit  9/3/2019  
Application received  8/29/2019 DONE
Application submitted via PDS Online on Aug 29 2019 8:25AM