INSP-Final Inspection | 7/31/2020 | 7/31/2020 | 7/31/2020 | P | PASS |
Jim Page
|
|
|
Final fire alarm inspection is complete.
|
Plan assigned to (Lee) | 7/30/2020 | | 7/31/2020 | | DONE |
Lee G Meredith
|
|
|
|
Intake Approval | | | 7/31/2020 | | PASS |
|
|
|
|
1st review completed | | | 7/31/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 7/31/2020 | | 7/31/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/31/2020 | | DONE |
|
|
|
As built - No fee.
|
Permit Ready to Issue | | | 7/31/2020 | | DONE |
|
|
|
as built approved
|
CHANGE STATUS TO (ISS) | | | 7/31/2020 | | DONE |
|
|
|
|
INSP-Final Inspection | 7/29/2020 | 7/30/2020 | 7/30/2020 | A | PART |
Jim Page
|
|
|
Fire alarm is compliamt with NFPA72, horns needed to be removed due too exceeding 110db. Plans are too be updated showing changes, permit can be finaled after cahnges are approved. 14 day TCO authorized pending fire alarm drawing update.
Coordinated with FA techician for 8AM, Brandon ###-####
|
Plan resubmittals received | | | 7/30/2020 | | DONE |
|
|
|
Zach with Johnson Controls uploading as builts
|
INSP-Final Inspection | 7/29/2020 | 7/29/2020 | 7/29/2020 | P | CANC |
Jim Page
|
|
|
Cancelled per conversation with point of contact, still troublshootoing area's were sound exceeds 110db.
SCREENED // James Phone #: ###-####
|
CHANGE STATUS TO (ISS) | | | 7/29/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 7/28/2020 | | 7/28/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/28/2020 | | DONE |
|
|
|
Plan mod passed. Minimum review fee due.
|
Permit Ready to Issue | | | 7/28/2020 | | |
|
|
|
**DO NOT REISSUE - PLAN MOD**
|
Plan Modification Accepted | | | 7/28/2020 | | DONE |
|
|
|
plan mod #6 requested by Dough - deviced was changed
|
Plan assigned to (Lee) | 7/28/2020 | | 7/28/2020 | | DONE |
Lee G Meredith
|
|
|
plan mod #6 requested by Dough - deviced was changed
|
Intake Approval | | | 7/28/2020 | | PASS |
|
|
|
|
1st review completed | | | 7/28/2020 | | DONE |
|
|
|
|
INSP-Final Inspection | 7/24/2020 | 7/27/2020 | 7/27/2020 | P | FAIL |
Jim Page
|
|
|
Areas have been adjusted due too sound levels exceeding 110db, plans need to reflect corrections. Smoke detecotr to close to wall HVAC unit, minimum 36 inches away is required. Level 3 room sounder bases did not function with general fire alarm in common areas. Provide weather proof mounting boxes for bathrooms with showers. Inspection stopped after level 3 sounder bases did not function.
Phone #: ###-#### Inspection requested via web by Brandon Higley
|
INSP-Final Inspection | 7/22/2020 | 7/23/2020 | 7/23/2020 | P | FAIL |
Jim Page
|
|
|
Provide small documents as discussed. Fire sprinkler monitoring is complete. Room notification did not function on general alarm.
Fire alarm inspection. Phone #: ###-#### Inspection requested via web by Ashley Chapman
|
Plan assigned to (Lee) | 7/17/2020 | | 7/20/2020 | | DONE |
Lee G Meredith
|
|
|
|
Intake Approval | | | 7/20/2020 | | PASS |
|
|
|
|
1st review completed | | | 7/20/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 7/20/2020 | | 7/20/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/20/2020 | | DONE |
|
|
|
Plan mod passed. No additional review comments provided. Base plan mod fee of $65 is due.
|
Permit Ready to Issue | | | 7/20/2020 | | DONE |
|
|
|
plan mod
|
CHANGE STATUS TO (ISS) | | | 7/20/2020 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 7/17/2020 | | DONE |
|
|
|
|
Plan Modification Accepted | | | 7/17/2020 | | DONE |
|
|
|
Updated asbuilts
|
Plan Modification Accepted | | | 7/13/2020 | | DONE |
|
|
|
|
Intake Approval | | | 7/13/2020 | | PASS |
|
|
|
|
1st review completed | | | 7/13/2020 | | PASS |
|
|
|
|
Alarm Plan Check | 7/13/2020 | | 7/13/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/13/2020 | | DONE |
|
|
|
Plan mod passed. No additional review comments provided. Base plan mod fee of $65 is due.
|
Permit Ready to Issue | | | 7/13/2020 | | DONE |
|
|
|
**PLAN MOD - DO NO REISSUE**
|
INSP-Alarm Testing | 6/25/2020 | 6/29/2020 | 6/29/2020 | P | CANC |
Troy Cobbley
|
|
|
Please call our tech Brian ahead of time to verify start time ###-####. Contractor is Doug at ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by James Schofield Inspection cancelled from web by: James Schofield
|
CHANGE STATUS TO (ISS) | | | 6/17/2020 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 6/9/2020 | | 6/15/2020 | | DONE |
Lee G Meredith
|
|
|
as built
|
Intake Approval | | | 6/15/2020 | | PASS |
|
|
|
|
1st review completed | | | 6/15/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 6/15/2020 | | 6/15/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/15/2020 | | DONE |
|
|
|
As built - No fee. Passed, subject to field inspection.
|
Permit Ready to Issue | | | 6/15/2020 | | DONE |
|
|
|
**AS BUILT - DO NOT REISSUE**
|
Plan resubmittals received | | | 6/9/2020 | | DONE |
|
|
|
as built requested per James Schofield of JOhnson Controls
|
Issue and Print Permit | | | 5/26/2020 | | DONE |
|
|
|
|
Plan Modification Accepted | | | 5/20/2020 | | DONE |
|
|
|
requested by Kristen
|
Plan assigned to (Lee) | 5/20/2020 | | 5/20/2020 | | DONE |
Lee G Meredith
|
|
|
adding in duct detenctors for air hadleling unit
|
Permit Ready to Issue | | | 5/20/2020 | | DONE |
|
|
|
**DO NOT REISSUE - PLAN MOD**
|
PLANS TAKEN FRONT DESK ALARM | | | 5/20/2020 | | DONE |
|
|
|
Plan mod passed. No additional review comments.
$65 minimum review fee due.
|
Alarm Plan Check | 5/20/2020 | | 5/20/2020 | | PASS |
Lee G Meredith
|
|
|
|
1st review completed | | | 5/20/2020 | | DONE |
|
|
|
|
Intake Approval | | | 5/20/2020 | | PASS |
|
|
|
|
Plan Modification Accepted | | | 5/20/2020 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 2/26/2020 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 2/25/2020 | | 2/25/2020 | | DONE |
Lee G Meredith
|
|
|
plan mod to relocate sprinkler monitoring locations
|
Plan Modification Accepted | | | 2/25/2020 | | DONE |
|
|
|
Work flow was requested to be opened for plan mod
|
1st review completed | | | 2/25/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 2/25/2020 | | 2/25/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 2/25/2020 | | DONE |
|
|
|
Plan Mod fee of $65.
Plan mod is to relocate sprinkler monitoring locations. No additional review comments provided.
|
Permit Ready to Issue | | | 2/25/2020 | | DONE |
|
|
|
plan mod approved
|
Issue and Print Permit | | | 10/25/2019 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/7/2019 | | DONE |
|
|
|
|
Alarm Plan Check | 10/7/2019 | | 10/7/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 10/7/2019 | | DONE |
|
|
|
Passed with comments.
|
Permit Ready to Issue | | | 10/7/2019 | | DONE |
|
|
|
|
Alarm Plan Check | 10/3/2019 | | 10/3/2019 | | FAIL |
Lee G Meredith
|
|
|
Resubmittal failed. Last 2 items on review correction list have not been addressed. Returned to Kristing with an email explaining the return.
|
Plan resubmittals received | | | 9/20/2019 | | DONE |
|
|
|
Resubmittals have been uploaded but all corrections have not been made. Returned to applicant.
|
Plan assigned to (Lee) | 9/10/2019 | | 9/10/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 9/10/2019 | | FAIL |
|
|
|
See 1st review comments.
|
Application received | | | 9/9/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 9 2019 2:33PM
|