Permit NumberFIR19-00684
StatusFinaled
Name APEX INTEGRATED SECURITY SOLUTIONS
Site Address 350 S ALLUMBAUGH WAY
Project NameMorning Star MC Door Holders A
Customer Number 
ePlanReviewYes
Description
Morning Star Memory Care Door Holders Add scope of work is to add 2 door holder and associated FA smoke detectors to an existing FA system. Original FA Installation is FIR17-00040. This work is not associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/23/201910/24/201910/24/2019APASS
DetailsTroy Cobbley
Permit finaled.

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
CHANGE STATUS TO (ISS)  10/22/2019 DONE
plan mod
Plan Modification Accepted  10/21/2019 DONE
change to release door holders using corridor area detection at the corridor side of doors. the other side of doors is unchanged (using single smoke detector with relay)
Plan assigned to (Lee)10/21/2019 10/21/2019 DONE
DetailsLee G Meredith
Plan Modification Accepted  10/21/2019 DONE
1st review completed  10/21/2019 PASS
Alarm Plan Check10/21/2019 10/21/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/21/2019 DONE
Plan mod approved. Review fee is $65 (min. fee)
Permit Ready to Issue  10/21/2019 DONE
INSP-Final Inspection10/16/201910/17/201910/17/2019AFAIL
DetailsTroy Cobbley
Tested all devices but the new smoke detector in the main corridor is not centered on the doors as required in nfpa 72.

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
Application received  9/10/2019 DONE
Application submitted via PDS Online on Sep 10 2019 7:10AM
Plan assigned to (Lee)9/10/2019 9/10/2019 DONE
DetailsLee G Meredith
1st review completed  9/10/2019 PASS
Alarm Plan Check9/10/2019 9/10/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/10/2019 DONE
Quick permit passed. No comments.
Permit Ready to Issue  9/10/2019 DONE
Issue and Print Permit  9/10/2019 DONE