INSP-Final Inspection | 3/13/2020 | 3/17/2020 | 3/17/2020 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Phone #: ###-#### Inspection requested via web by Sam Ball
|
INSP-Final Inspection | 3/12/2020 | 3/13/2020 | 3/13/2020 | A | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### Inspection requested via web by Sam Ball
|
INSP-Final Inspection | 2/3/2020 | 2/4/2020 | 2/4/2020 | A | CANC |
Troy Cobbley
|
|
|
Still waiting for Delta to provide permit for the fire alarm work performed in the other portions of the building. Phone #: ###-#### Inspection requested via web by Sam Ball
|
Plan assigned to (Lee) | 1/10/2020 | | 1/13/2020 | | DONE |
Lee G Meredith
|
|
|
as builts
|
1st review completed | | | 1/13/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 1/13/2020 | | 1/13/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/13/2020 | | DONE |
|
|
|
As built - No Fee.
|
CHANGE STATUS TO (ISS) | | | 1/13/2020 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/13/2020 | | DONE |
|
|
|
as built approved
|
Plan resubmittals received | | | 1/10/2020 | | DONE |
|
|
|
Workflow was requested to be re opened for as builts.
|
INSP-Final Inspection | 11/21/2019 | 11/22/2019 | 11/22/2019 | A | FAIL |
Troy Cobbley
|
|
|
Provide plan mods showing the two changes of the wall mouted strobes to higher candella. Provide sync'ing of the audible/horn as per NFPA 72 18.4.2.4 and 3.3.317.1.
We are requesting the final for 7:30 because there are several restaurants and businesses that could be affected when alarm is set off. Thank You. Phone #: ###-#### Inspection requested via web by Sam Ball
|
Issue and Print Permit | | | 9/16/2019 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 9/13/2019 | | 9/13/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 9/13/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 9/13/2019 | | 9/13/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 9/13/2019 | | DONE |
|
|
|
Passed with review comments.
|
Permit Ready to Issue | | | 9/13/2019 | | DONE |
|
|
|
MET
|
Application received | | | 9/10/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 10 2019 2:27PM
|