INSP-Final Inspection | 12/11/2019 | 12/12/2019 | 12/12/2019 | P | PASS |
Jim Page
|
|
|
Per email from Romeo Gervias Boise City Deputy Chief FIre Marshal and Lee Meridith Fire Alarm Plans Examiner, RTU units can shut down individually instead of all together, final fire alarm inspection for scope of work is complete.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
INSP-Final Inspection | 12/4/2019 | 12/5/2019 | 12/5/2019 | P | PART |
Jim Page
|
|
|
Fan shutdown on water flow verified. Will verify if all 4 RTU units need to shutdown during in duct smoke detector activation or if individual unti shutdown is approved.
Call prior to going Phone #: 2089546009 >> Inspection requested via mobile web by Kenny Leslie
|
INSP-Final Inspection | 10/31/2019 | 11/1/2019 | 10/31/2019 | A | PART |
Jim Page
|
|
|
Fire sprinkler riser monitoring for TCO is complete, previously noted item for the double alarm showing up on monitoring has been corrected. Remaining items to be inspected at a later date.
|
INSP-Final Inspection | 10/22/2019 | 10/23/2019 | 10/23/2019 | A | FAIL |
Troy Cobbley
|
|
|
Tested only the interconnect with the wet system tamper switches and flow switches, other devices have not been connected yet. The monitoring company received the wrong count of signals.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
Plan assigned to (Lee) | 9/19/2019 | | 9/19/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 9/19/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 9/19/2019 | | 9/19/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 9/19/2019 | | DONE |
|
|
|
Passed with comments.
|
Permit Ready to Issue | | | 9/19/2019 | | DONE |
|
|
|
met
|
Issue and Print Permit | | | 9/19/2019 | | DONE |
|
|
|
|
Application received | | | 9/17/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 17 2019 12:37PM
|