INSP-Final Inspection | 11/14/2019 | 11/14/2019 | 11/14/2019 | A | PASS |
Jim Page
|
|
|
Final inspection for hood suppression system complete.
|
INSP-Final Inspection | 9/30/2019 | 9/30/2019 | 9/30/2019 | P | CANC |
Jim Page
|
|
|
Hood suppression system is not integrated with the fire alarm system as of this entry, hood suppression system must be tied into fire alarm system before final acceptance inspection, per conversation with point of contact, this request is cancelled and will be rescheduled when fire alarm integration is complete.
Robert is the contact. Phone #: ###-#### Inspection requested via web by Scott Corriea
|
Issue permit | | | 9/30/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/30/2019 | | DONE |
|
|
|
This permit was created on the web by Scott Corriea
|