INSP-Final Inspection | 7/1/2020 | 7/2/2020 | 7/2/2020 | A | PASS |
Greg Ruxton
|
|
|
South riser flow switch previously noted as not working retested to verify operational status. Leak in inspectors test previously noted repaired and tested.
Call Anthony before heading out. Corrected items from yesterday’s inspection, ready to re-inspect. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Final Inspection | 7/1/2020 | 7/1/2020 | 7/1/2020 | P | FAIL |
Troy Cobbley
|
|
|
Leak needs repaired and south flow switch did not function. Anytime after 11am, call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in/Hydro | 5/11/2020 | 5/12/2020 | 5/13/2020 | A | PASS |
Troy Cobbley
|
|
|
Overhead hydro witnessed.. Call James before heading out! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in/Hydro | 5/7/2020 | 5/11/2020 | 5/11/2020 | A | FAIL |
Troy Cobbley
|
|
|
Contact could not meet at the same time I could. Will need to be rescheduled. Overhead hydro, call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 1/8/2020 | 1/9/2020 | 1/9/2020 | A | PASS |
Troy Cobbley
|
|
|
Tenting re-inspection passed. Piping can be covered. , call James when heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 1/8/2020 | 1/8/2020 | 1/8/2020 | P | CANC |
Jim Page
|
|
|
Call James before heading out, tenting re-inspection Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
INSP-Sprinkler Rough-in | 1/6/2020 | 1/7/2020 | 1/7/2020 | A | CANC |
Troy Cobbley
|
|
|
To be canceled per James and rescheduled for tomorrow.
Tenting inspection, call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 1/3/2020 | 1/6/2020 | 1/6/2020 | A | FAIL |
Troy Cobbley
|
|
|
The tenting has been removed from a section of pipe. I sent a picture to James. No piping to be covered.
Tenting Re-Inspection, call James when heading out. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 1/2/2020 | 1/3/2020 | 1/3/2020 | A | CANC |
Troy Cobbley
|
|
|
Tenting re-inspection, call James when heading out. Thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
INSP-Sprinkler Rough-in | 12/31/2019 | 1/2/2020 | 1/2/2020 | A | PART |
Troy Cobbley
|
|
|
Hangers have been corrected but the insulation still needs some work. We agreed to come back in the morning after corrections have been made.
Overhead rough ; tenting, call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 12/31/2019 | 1/2/2020 | 12/31/2019 | A | CANC |
Troy Cobbley
|
|
|
Tenting inspection, call before heading out. Thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
INSP-Sprinkler Rough-in | 12/25/2019 | 12/27/2019 | 12/27/2019 | P | FAIL |
Jim Page
|
|
|
Tenting not installed correctly in numerous areas, cover is not approved.
Overhead rough and tenting. Call James before heading out. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 12/23/2019 | 12/26/2019 | 12/25/2019 | A | CANC |
Troy Cobbley
|
|
|
Call James before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
Issue and Print Permit | | | 11/12/2019 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/30/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 10/30/2019 | | 10/30/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/30/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 10/30/2019 | | DONE |
|
|
|
met
|
Sprinkler Plan Check | 10/24/2019 | | 10/29/2019 | | FAIL |
Mark Stumbaugh
|
|
|
|
1st review completed | | | 10/29/2019 | | FAIL |
Mark Stumbaugh
|
|
|
|
Intake Approval | | | 10/24/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 10/24/2019 | | 10/24/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Application received | | | 10/23/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Oct 23 2019 11:30AM
|