Permit Information
Permit NumberFIR19-00883
StatusFinaled
Name PROTEX
Site Address 9300 W OVERLAND RD Unit: SUITE 200
Project NameUnitek 2nd Floor
Customer Number 
ePlanReviewYes
Description
Add Fire extender panel and notification to existing FACP. This work is associated with building permit BLD19-03898.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/13/20203/13/20203/13/2020PPASS
DetailsTroy Cobbley
Permit finaled.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection2/25/20202/25/20202/25/2020PPART
DetailsTroy Cobbley
A temporary for this permit has been given for 90 days. To final this permit the new notification devices need to sync with the existing notification devices as per NFPA 72.

Contact is Dirk. Building has been tested and verified for synchronization. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Permit Ready to Issue  2/25/2020 DONE
as built approved
CHANGE STATUS TO (ISS)  2/25/2020 DONE
INSP-Final Inspection2/24/20202/24/20202/24/2020PFAIL
DetailsTroy Cobbley
Not all of the strobes have been modified to meet the minimum spacing requirements of NFPA 72. There are strobes on the exterior balcony that are not shown on the plans. They will need to be shown if they are powered from the new NAC panel.


Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan resubmittals received  2/24/2020 DONE
as built
Plan assigned to (Lee)2/24/2020 2/24/2020 DONE
DetailsLee G Meredith
1st review completed  2/24/2020 DONE
Alarm Plan Check2/24/2020 2/24/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/24/2020 DONE
As built - No fee.
Plan Modification Accepted  2/24/2020 DONE
1st review completed  2/24/2020 DONE
Alarm Plan Check2/24/2020 2/24/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/24/2020 DONE
2nd as built passed. Minimum plan mod review fee of $65 is due.
Permit Ready to Issue  2/24/2020 DONE
plan mod passed
CHANGE STATUS TO (ISS)  2/24/2020 DONE
INSP-Final Inspection2/21/20202/21/20202/21/2020PFAIL
DetailsTroy Cobbley
No testing performed. During walk through I fould many of the strobes overspaced and areas missing notificaiton. Contractor needs to perform a walk through and modify coverage to meet min. code. Plans need to be resubmitted showing the changes for approval before the next scheduled inspection.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
Plan resubmittals received  2/21/2020 DONE
Morgan from ProTex called asking to start an as built workflow
Plan assigned to (Lee)2/21/2020 2/21/2020 DONE
DetailsGemma Flores
as built
Permit Ready to Issue  2/21/2020 DONE
as built approved
Issue and Print Permit  2/21/2020 DONE
Plan resubmittals received  2/20/2020 DONE
as built- per Morgan request duct detector addition
Plan assigned to (Lee)2/20/2020 2/20/2020 DONE
DetailsLee G Meredith
as built- per Morgan request duct detector addition
1st review completed  2/20/2020 DONE
Alarm Plan Check2/20/2020 2/20/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/20/2020 DONE
As built - No fee.
INSP-Final Inspection2/5/20202/6/20202/5/2020PCANC
DetailsTroy Cobbley
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
Plan assigned to (Lee)11/25/2019 11/25/2019 DONE
DetailsLee G Meredith
Intake Approval  11/25/2019 PASS
1st review completed  11/25/2019 DONE
Alarm Plan Check11/25/2019 11/25/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  11/25/2019 DONE
Passed with comments and noted requirements on floor plan drawing.
Permit Ready to Issue  11/25/2019 DONE
met
Issue and Print Permit  11/25/2019 DONE
Application received  11/22/2019 DONE
Application submitted via PDS Online on Nov 22 2019 1:16PM