INSP-Final Inspection | 6/18/2020 | 6/19/2020 | 6/19/2020 | P | PASS |
Jim Page
|
|
|
Final inspection for underground supply complete.
Jeff Chaney is the contact Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 6/18/2020 | 6/19/2020 | 6/19/2020 | A | FAIL |
Jim Page
|
|
|
Wrong permit requested for type of inspection.
This is a Fire Pump Final. Contact is Jeff Chaney Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Final Inspection | 6/18/2020 | 6/19/2020 | 6/18/2020 | A | CANC |
Jim Page
|
|
|
The contact is Jeff Chaney. Have a good day!! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 6/17/2020 | 6/18/2020 | 6/18/2020 | A | PASS |
Troy Cobbley
|
|
|
The overhead hydro for the five systems was witnessed with no pressure loss. Header, FDC and fire pump piping was not tested.
Jeff Chaney is the contact. Thanks so much! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 6/17/2020 | 6/17/2020 | 6/17/2020 | P | DONE |
Jim Page
|
|
|
Hydrostatic test for underground supply witnessed via photo, no pressure loss observed by timed photos.
Jeff Chaney is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Supply line flush | 6/16/2020 | 6/17/2020 | 6/17/2020 | A | DONE |
Jim Page
|
|
|
Main line underground flush complete.
Jeff Chaney is the contact. Thanks so much! Phone #: ###-#### Inspection requested via web by Stan Beus, coordinated for 0830 flush time with SUEZ.
|
INSP-Supply line flush | 6/16/2020 | 6/16/2020 | 6/16/2020 | P | CANC |
Jim Page
|
|
|
Flush rescheduled for 17JUNE2020 per conversation with SUEZ and point of contact. Could not flush until water sample acceptance for the new water service.
Jeff Chaney is the contact. Thanks so much! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Supply line flush | 6/12/2020 | 6/15/2020 | 6/15/2020 | P | CANC |
Jim Page
|
|
|
Cancelled per conversation with point of contact, will be rescheduled for a later date.
Jeff Chaney is the contact Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 6/9/2020 | 6/9/2020 | 6/9/2020 | P | PASS |
Troy Cobbley
|
|
|
The two thrust blocks have been replaced. These sections of pipe can be covered.
Bryan Collins Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 6/8/2020 | 6/8/2020 | 6/8/2020 | P | PART |
Troy Cobbley
|
|
|
I gave the ok to cover on the remaining underground piping except for the two east most thrust blocks. These two thrust blocks have pulled/fallen away from the underground supply piping and will need to be repoured, re-inspected, prior to an ok for cover.
Bryan Collins is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 2/11/2020 | 2/12/2020 | 2/12/2020 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for IBR complete, IBR approved for cover, remaining underground to be installed at a later date.
Bryan Collins is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
Issue and Print Permit | | | 12/3/2019 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/3/2019 | | DONE |
|
|
|
|
Sprinkler Plan Check | 11/27/2019 | | 12/2/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
1st review completed | | | 12/2/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/2/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 12/2/2019 | | DONE |
|
|
|
met
|
Application received | | | 11/27/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Nov 27 2019 7:59AM
|
Intake Approval | | | 11/27/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 11/27/2019 | | 11/27/2019 | | DONE |
Mark Stumbaugh
|
|
|
|