Permit Information
Permit NumberFIR19-00902
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 6101 N PIERCE PARK LN
Project NameSolace House
Customer Number 
ePlanReviewYes
Description
Provide a full manual fire alarm system with sprinkler monitoring and low frequency sounder bases in sleeping rooms. System was engineered by E2CO. This work is associated with building permit BLD19-01649.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/17/20207/17/20207/17/2020PPASS
DetailsJim Page
Final fire alarm inspection is complete.

Phone #: ###-#### Inspection requested via web by Robert Gobler
INSP-Final Inspection7/15/20207/15/20207/15/2020PFAIL
DetailsJim Page
Smoke detectors are over spaced, add/relocate as discussed, plans will need to be revisedand submitted for corrections. Provide map showing initiating devices and place at FACP.

Phone #: ###-#### Inspection requested via web by Robert Gobler
Plan resubmittals received  7/14/2020 DONE
Justin requested the work flow to be opened for as builts.
Plan assigned to (Lee)7/14/2020 7/14/2020 DONE
DetailsLee G Meredith
as builts
Intake Approval  7/14/2020 PASS
1st review completed  7/14/2020 DONE
Alarm Plan Check7/14/2020 7/14/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  7/14/2020 DONE
Plan mod passed. Minimum review time is due.
Permit Ready to Issue  7/14/2020 DONE
**PLAN MOD - DO NOT REISSUE**
CHANGE STATUS TO (ISS)  7/14/2020 DONE
INSP-Final Inspection7/10/20207/10/20207/10/2020PFAIL
DetailsTroy Cobbley
Need plan mods showing the communication method and the Sleeping area strobes need to meet NFPA 72 for the use of 110cd or 177cd as far as distance from ceiling as discussed. Need larger access to the east attic heat detector. Need the FACP shown upstairs instead of downstairs. Need to relocate or add a smoke detector in the basement as discussed. Plans show a PIV but none has been installed. See the city approved plans for corrections marked in red. No actual devices tested. Phone #: ###-#### Inspection requested via web by Robert Gobler
Intake Approval  12/9/2019 PASS
Alarm Plan Check12/9/2019 12/9/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/9/2019 DONE
Passed as noted on drawings.
Permit Ready to Issue  12/9/2019 DONE
met
Issue and Print Permit  12/9/2019 DONE
Plan assigned to (Lee)12/3/2019 12/3/2019 DONE
DetailsLee G Meredith
Intake Approval  12/3/2019 FAIL
Needs engineer of record approval and audible notifiation does not appear to be adequate. Returned to applicant.

12-4-19 Mary indicated that there are sounder bases so audibility will be adequate. She also noted that the engineer of record wont respond to her. I responded to say the engineer of record review / approval is required and that I need it by 12-5-19 before returning the submittal. Suggested that she contact the general contractor or architect.

12-5-19: No resubmittal with EOR approval so returned to Mary.
Application received  12/2/2019 DONE
Application submitted via PDS Online on Dec 2 2019 3:40PM