INSP-Final Inspection | 3/31/2020 | 4/1/2020 | 4/1/2020 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, final inspection for this scope of work is complete.
Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
CHANGE STATUS TO (ISS) | | | 2/26/2020 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/26/2020 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 2/21/2020 | | 2/24/2020 | | DONE |
Lee G Meredith
|
|
|
2nd as built
|
Plan Modification Accepted | | | 2/24/2020 | | DONE |
|
|
|
|
1st review completed | | | 2/24/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 2/24/2020 | | 2/24/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 2/24/2020 | | DONE |
|
|
|
$65 minimum plan mod fee.
|
Permit Ready to Issue | | | 2/24/2020 | | DONE |
|
|
|
plan mod approved
|
CHANGE STATUS TO (ISS) | | | 2/21/2020 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/21/2020 | | DONE |
|
|
|
2nd as built request per Kristin from Johnson Controls
|
1st review completed | | | 2/5/2020 | | DONE |
|
|
|
|
Alarm Plan Check | 2/5/2020 | | 2/5/2020 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 2/5/2020 | | DONE |
|
|
|
As built - No fee
|
Permit Ready to Issue | | | 2/5/2020 | | DONE |
|
|
|
as built approved
|
Plan resubmittals received | | | 2/4/2020 | | DONE |
|
|
|
Per christin at johnson controls. Submitting for as builts
|
Plan assigned to (Lee) | 2/4/2020 | | 2/4/2020 | | DONE |
Lee G Meredith
|
|
|
as builts
|
INSP-Final Inspection | 1/31/2020 | 2/3/2020 | 2/3/2020 | A | FAIL |
Jim Page
|
|
|
Speaker strobe in kitchen area is overspaced. A/V device wiring in seating area is attached to fire sprinkler piping, not allowed to attach to sprinkler piping per NFPA13. Three A/V devices in tenant space experience a double flash during active alarm, troubleshoot double flash issue and repair, A/V devices will be required to be activated during next inspection.
Brian Phone #: ###-####
|
INSP-Final Inspection | 1/28/2020 | 1/31/2020 | 1/31/2020 | A | FAIL |
Jim Page
|
|
|
Inspection request was not coordinated with inspector, start time for inspector is 8AM unless approved by the fire section supervisor for a 7AM inspection time, as stated before on past inspections, 7AM inspection time needs to be coordinated with the inspector and approved by the fire section supervisor per notification to the fire section supervisor by the inspector.
Building is occupied - 7 am schedule Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
Issue and Print Permit | | | 12/18/2019 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 12/17/2019 | | 12/17/2019 | | DONE |
Lee G Meredith
|
|
|
|
Intake Approval | | | 12/17/2019 | | PASS |
|
|
|
|
1st review completed | | | 12/17/2019 | | DONE |
|
|
|
|
Alarm Plan Check | 12/17/2019 | | 12/17/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 12/17/2019 | | DONE |
|
|
|
Passed. No written review comments provided.
|
Permit Ready to Issue | | | 12/17/2019 | | DONE |
|
|
|
MET
|
Application received | | | 12/16/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Dec 16 2019 10:19AM
|