Permit Information
Permit NumberFIR19-00934
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION
Site Address 150 N 8TH ST
Project NameCapital Terrace Taphouse Speak
Customer Number 
ePlanReviewYes
Description
Capital Terrace Taphouse Speaker- MODIFY EXISTING FIRE ALARM SYSTEM: THE SCOPE OF WORK FOR THIS PROJECT IS TO REMOVE ALL EXISTING NOTIFICATION DEVICES WITHIN THE
TENANT SPACE & INSTALL NEW NOTIFICATION DEVICES AS NOTED ON PLANS.
THE NEW SPEAKER WIRING TO BE CLASS A AND VISUAL CIRCUIT TO BE CLASS B.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/31/20204/1/20204/1/2020APASS
DetailsJim Page
Previously noted items have been corrected, final inspection for this scope of work is complete.

Phone #: ###-#### Inspection requested via web by Kristin Dolan
CHANGE STATUS TO (ISS)  2/26/2020 DONE
Issue and Print Permit  2/26/2020 DONE
Plan assigned to (Lee)2/21/2020 2/24/2020 DONE
DetailsLee G Meredith
2nd as built
Plan Modification Accepted  2/24/2020 DONE
1st review completed  2/24/2020 DONE
Alarm Plan Check2/24/2020 2/24/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/24/2020 DONE
$65 minimum plan mod fee.
Permit Ready to Issue  2/24/2020 DONE
plan mod approved
CHANGE STATUS TO (ISS)  2/21/2020 DONE
Plan resubmittals received  2/21/2020 DONE
2nd as built request per Kristin from Johnson Controls
1st review completed  2/5/2020 DONE
Alarm Plan Check2/5/2020 2/5/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/5/2020 DONE
As built - No fee
Permit Ready to Issue  2/5/2020 DONE
as built approved
Plan resubmittals received  2/4/2020 DONE
Per christin at johnson controls. Submitting for as builts
Plan assigned to (Lee)2/4/2020 2/4/2020 DONE
DetailsLee G Meredith
as builts
INSP-Final Inspection1/31/20202/3/20202/3/2020AFAIL
DetailsJim Page
Speaker strobe in kitchen area is overspaced. A/V device wiring in seating area is attached to fire sprinkler piping, not allowed to attach to sprinkler piping per NFPA13. Three A/V devices in tenant space experience a double flash during active alarm, troubleshoot double flash issue and repair, A/V devices will be required to be activated during next inspection.

Brian Phone #: ###-####
INSP-Final Inspection1/28/20201/31/20201/31/2020AFAIL
DetailsJim Page
Inspection request was not coordinated with inspector, start time for inspector is 8AM unless approved by the fire section supervisor for a 7AM inspection time, as stated before on past inspections, 7AM inspection time needs to be coordinated with the inspector and approved by the fire section supervisor per notification to the fire section supervisor by the inspector.

Building is occupied - 7 am schedule Phone #: ###-#### Inspection requested via web by Kristin Dolan
Issue and Print Permit  12/18/2019 DONE
Plan assigned to (Lee)12/17/2019 12/17/2019 DONE
DetailsLee G Meredith
Intake Approval  12/17/2019 PASS
1st review completed  12/17/2019 DONE
Alarm Plan Check12/17/2019 12/17/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/17/2019 DONE
Passed. No written review comments provided.
Permit Ready to Issue  12/17/2019 DONE
MET
Application received  12/16/2019 DONE
Application submitted via PDS Online on Dec 16 2019 10:19AM